Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

in thermal overload relay class 10A indicate what

Answer Posted / paul

I am not aware of Class 10A, I am aware of Class 5, 10, 15,
20, 25 & 30. These refer to the tripping curve of a
thermal/electronic relay - eg Class 10 means 6 x motor full
load current (FLC) for 10 seconds (normal squirrel cage
induction motor). Therefore Class 30 means 6 x FLC for 30
seconds and Class 5 means 6 x FLC for 5 seconds etc....

Is This Answer Correct ?    19 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

during installation time of transformer and alternator which points we have to observed?

2012


According to underground cables a) stress b/w sheath & conductor is high b) inrush of core & conductor

2029


How to calculate mf when meter equipment and meter are connected

1790


If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?

2333


State the factors, for the choice of electrical system for an aero turbine.

1224


What is K-rated transformer? What is the use of it? What can be the size(pls provide calculation if possible) of K- factor transformer for 550kW,690V motor operating with drive (VFD)?

2328


Differentiate between ideal and non-ideal voltage sources?

1160


WHY MOSTLY Rph IS USED FOR CONTROL CIRCUITS AUX. SUPPLY ?

2565


How do I calculate/select Droop CT ratio for various capacity of generators?

3715


what is the function and use of cable differential protection relay?

2968


can anybody send the rrb chennai &rrb bopal question papers of 2006&2007.My exam is on 12 oct 2008.Its urgent

2097


I want to merge a cable..in between two metering Cubicals which contains CT's and PT's and Energy meter..before taking merger..what are the common things required?

1715


If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)

2324


How to work E.L.C.B and how to connect in circuit.

2061


What is the reason for using a GE G101 MCB in place of an EP102 MCB if both are capable of AC circuit protection?

2717