Answer Posted / ars326
The AVR derives its power supply from the line to neutral
terminals of the AC Generator,at a level of 240V AC RMS at
50/60 hz.The sensing voltage,which is regulated voltage is
derived from the line to line terminals of the AC
Generator.The AVR forms an important part of the closed loop
system comprising of the generator field,generator armature
and the AVR.
The AVR,first builds up the generator voltage from its
residual levels to the rated value of 415V.when the
generator is loaded,the sensed voltage goes down and
generates the error voltage,which is required to drive the
closed loop system.The AVR contains a high gain
amplifier,ramp and pedestal circuitry.depending upon the
value of the amplified voltage either high or low the ramp
intersects the amplified volatage at a point which is early
or late in the half cycle.at the intersection point,a firing
pulse is produced to trigger the power device.
When the power device is trigerred early in the half
cycle,more voltage is let into the field and when trigerred
late in the half cycle,less voltage is let into the field.
in order to reduce the generated voltage at lower speed,a
signal inversely proportion to the speed is fed as an extra
input.At higher speeds,the effect is nil while at lower
speeds the voltage reduces more than proportionate with the
speed.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?
What is a single phase autotransformer?
Why did lightening arrestor solid copper rod head is sharp on mobile tower top?
how many current required for hypo test
which type of stability limit is higher,steady state or transient? why?
State The Difference Between Generator And Alternator?
'documenˁ
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor
RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?
PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.
What is the armature mmf in a D.C machine?
how test transfomer(3 phase75kva) by megger
What is installed in PAC that is control the humidity