Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)

Answer Posted / satyajit sadhu

FAULT LEVEL MEANS SHORT CIRCUIT CAPACITY OF TRANSFORMER.YOU
HAVE NOT MENTIONED THE VALUE OF TRANSFORMER RATIO & % OF
IMPEDENCE.ASSUMED VOLTAGE RATIO= 11KV/415 V & % OF
IMPEDENCE=6%.
RATED FULL LOAD AMP OUTPUT =1MVA/(415 X 1.732)=1391.25A
SO SHORT CIRCUIT CAPACITY OF TRANSFORMER= 1391.25/6%
=23187.44 A
IF ANY FAULT OCCURED THEN THE ABOVE TRANSFORMER WITHSTAND
THE SHORT CIRCUIT CURRENT OF 23187 A.

Is This Answer Correct ?    33 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how do we calculate length of starting time and repeated starting of a direct online starter?

2031


According to underground cables a) stress b/w sheath & conductor is high b) inrush of core & conductor

2026


Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.

3403


What is the function of the generator exciter?

1467


How many types of circuit loads are there in a common electrical circuit?

1204


Can I use star delta connected induction motor for dual supply voltage?

2003


Is it possible to measure the voltage of a battery from a single terminal?

1789


Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?

1484


What is clock position of Transformer?what are the clock positions are there?and what is different of them?

3206


What are the three types of compensators?

1147


What are the effects of electrical faults?

1076


In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..

2002


how to calculate vfd o/p voltage by frequency

2207


what is the power rating of CPU, CRT type moniter, LCD type moniter,scanner Approx.

2266


What is your acheivements

2214