I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)
Answer Posted / satyajit sadhu
FAULT LEVEL MEANS SHORT CIRCUIT CAPACITY OF TRANSFORMER.YOU
HAVE NOT MENTIONED THE VALUE OF TRANSFORMER RATIO & % OF
IMPEDENCE.ASSUMED VOLTAGE RATIO= 11KV/415 V & % OF
IMPEDENCE=6%.
RATED FULL LOAD AMP OUTPUT =1MVA/(415 X 1.732)=1391.25A
SO SHORT CIRCUIT CAPACITY OF TRANSFORMER= 1391.25/6%
=23187.44 A
IF ANY FAULT OCCURED THEN THE ABOVE TRANSFORMER WITHSTAND
THE SHORT CIRCUIT CURRENT OF 23187 A.
| Is This Answer Correct ? | 33 Yes | 4 No |
Post New Answer View All Answers
What is difference between YNyn0 and YNyn ??
how single phase preventer works ?
After synchronization with grid what is the demand value QKVAR and how we will maintain that?
Iin ESP why positive is grounded ? why not negative ?
How does a battary stores charge in it? please explain in simple manner and in detail.thanks
What is shunt voltage and u v voltage witch one best
Transformer diagram mention each parts ?
What is the difference between rulling span and wind span of of an Over Head Transmission Line?
what is the electrical?
Write down the brushes of a de machine.
if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
full form of flry b
sir my exam is on 19/6/2013 under electrical branch pls send me sample aptitude questions as well as sample technical questions for jindal steel and power company
How you calculating the 30 Hp 3 phase AC motor of power what size of cable is used for this motor?