what is the effect of PF on alternator sizing?
Answer Posted / kalidassallinterview
Generaly the generator is run in lagging power factor only.
If we tryed to increase the power factor to unity, then the
generator will be overloaded.Ex: 750KVA,0.8PF generator we
can connect up to 600KW load. If we increase the power
factor to unity there is a chace to connect extra true
power up to 750KW. so the engine will be load.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
there are cam operated switches - why we call cam operated , What is cam ?
what is the difference between capacitive and resistive voltage divider?
Why HT 11 KV Slipring Motors are connected in star ?
What are the special cables required for explosion proof wiring?
In a voltage-controlled current source A A current booster is never used B The load is always floated C A stiff current source drives the load D The load current equals Isc
Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.
What is the necessary and sufficient condition for stability.
What is the main purpose of c.f.b.c.boiler
2. Modify your design in question 1.a so that the circuit works according to the following function table X Y F 0 0 Clear 0 1 No Change 1 0 Parallel Loading 1 1 Count 3. Design a circuit that detects the pattern 010 in a serial input X considering: 3.a Overlapping 3.b No overlapping
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
How each of the following losses occur in d.c machines (i) copper (2)core (3) windage (4)friction please help me
Explain thin film resistors and wire-wound resistors
why is the power generator connected as star earthed or star earthed through reactance and what its features ?
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?