if power factor comes in leading & showing -0.95. Is there
any effect on electrical system? if yes, then please tell me
what would be the effects. & how long we keep power factor
in leading.
Keeping power factor in leading shows more KW & less KVA is
it correct or not.
Answer Posted / santosh kawade
It is not recommended to keep power factor leading:
1) We try to keep power factor unit to reduce transmission
losses, this main purpose will not achieved by keeping
leading power factor. If power factor is lower than unit
(it can be leading or lagging) transmission loss will
increase.
2) During leading power factor if we make any breaker
operation (close/open)it will generate high voltage across
breaker, which is harmful to breaker. For capacitive load
operation we need a special breaker.
3) It is not correct that keeping leading power factor
shows more KW and less KVA.
Santosh Kawade
9224 69 3116
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Is it required to use Automatic transfer Switch in L&T panel board if we use AMF panel with DG set? How the single line diagram will be? Please forward the material to sreenu_207@yahoo.co.in
we use capister for power factor. when we use capaciter in dg circuit than defect dg. can we use capaciter bank for dg circuit
A d.c. Shunt motor is found suitable to drive fans because they require?
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
working principle a.v.r. ?
How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?
What is limitedly stable system?
Can we put 3 layers of cable tray while installing tray
Why transformer used in UPS??
What is Control & Relay Panel? And Remote Control Center?
we have an energy meter in a capacitor bank panel, So should we consider it's readings as energy consumption on daily basis. (when capacitor bank doesn't have any energy losses)
can anybody send me syllabus of rrb section engg (electrical). and also send previous question pepar...
If mutual flux is 1.2wb & power factor is 0.8 lag , then what is the Useful flux of a transformer?
explain supply side and demand side energy management with advantages & disadvantages
Why does the radius of armature is less than the radius of pole shoe?