Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

We have a 12MW power plant & we inject 5-6MW power to
Orissa GRID. For this we have a 33KV/11KV switch yard
having 12.5MVA power transformer. Some times we draw power
during emergency. It is observed that during Export or
Import for load less than 500Kw the power factor is
decreasing to 0.3 . This is happening only during export or
import. During island condition TG power factor OK.Our
capacitor bank is provided with our Power plant auxilliary
load. Please suggest how I can we improve our power factor
during low load (GRID).

Answer Posted / velusamy

This problem can be solved by switching off all capacitor
banks during low load. we have faced Similar type of
problem in our cement plant loads which are fluctuating in
nature which causes export / import of power fluctuation(
loads go +500kw and - 500kw withing 1 or two seconds).

The main reason for this low power factor is due to
reactive power consumption of your 12.5 MVA power
transformer.

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how did the testing of protection relays done through current injection

2089


How the capacitance og capacitor volatage transformer is decided?

1970


what are all types of cross section in AC cables?

2299


how to select automotive wire by mathematical equation with given current, vlotage and resistance

2358


how pt is using

1951


ACCORDING TO IEC WHAT SHOULD BE THE MINIMUM HEIGHT OF G.I. STRUCTURE OF CT, PT, ISOLATOR, LA?

2204


what is the need of starter in tube light and what type of starter is used in that?

2024


What are gain margin and phase margin?

1388


why connecting surge unit in contactor coil

1886


why we used ZNO in Lightning arrester.

2003


how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.

2410


what is the differance between HT motors And LT MOTORS.

1980


HOW DO YOU CAN CHECK A 15KV DIODE, WHETHER IT IS OK OR NOT?

2049


What is difference between start imitation and start interlock for 3 phase motor protection ?

2251


what is the standard duration after failure EB power

1839