what is the effect of connecting three phase supply lines
to three phase auto transformer output terminals through a
fuse of 10Amp and a circuit breaker (MCB). Is this
connection permanently destroy the transformer?
Answer Posted / guest
1)Why would you want to connect the supply lines to the
output of an autotransformer?
2)The reversal of what you have chosen will happen. that is
if you had connected the higher than normal tapping of the
transformer with the supply than you will get a lower supply
at the input side.
3a)The 10amp fuse and MCB connected depends on how big is
your autotxformer.
3b)When you connect an MCB OR a fuse to a 3 phase
transformer and if one of the fuses or MCB breaks than single
phasing happens in the circuit which is not good.If you must
protect use a three pole reliable MCB only.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
following are the questions asked in interviews: 1) Considering the short circuit fault, which switchgear is preferable, SFU OR MCCB? Which operates faster? whicg one is popular in Indian Market and why? 2)Define SCPD. What is type2 coodination? 3)Why the contactor rating is higher for the fuseless selection than for fuse selection? whether the ratinf of SFU or MCCB remains the same in both the cases? 4)If the HP rating is known then can you calculate the ratings of L.V Switchgear(SFU/MCCB, contactor, OLR) without using the selection chart?
what is sustainable current of any conductors . a bare busbar or pvc cable has different sustainable current .
Why open circuit test of transformers is conducted at rated voltage??Why not any other voltage??
What's mean HVF & HAF in Vacuum Circuit Breaker?
why power factor is important?
What are the basic & Majour problems in UPS ?
PLS SEND THE RRB CHENNAI MODEL QUESTION PAPER my email id is ganesan98655@rediffmail.com
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
What are the ratings of VCB, MCB, MCCB, SF6, ACB, and OCB?
why swityard is necessrry requirement in any bis power distributin systems?
what is formula for calculate thermal overload in new numiricalrelay( not in bimetal relay)?
what is the string efficiency
sir, what is the importance of Fault MVA. how to calculate fault mva of 33kv substation connected by 6.5 km line(single circuit with equal spacing) with 110/11kv transformer in 110kv susbstation.the fault mva on 11 kv bus in 110kv susbstation is 208mva.