Answer Posted / pillay
Any AC electrical equipment that has conductors have to be rated in voltage and amps, so it is KVA if more than thousand. WHY.
SIMPLE . If more than the designed amps flows through the equipment it will over heat and burn.(destroyed)
IF a 500 kw transformer is loaded at 415 v at unity pf to the max it will carry 500000/415x1.732 = 695 amps
if the same transformer is loaded at 500kw at 415 v but at 0.5 pf it will carry 500000/415x1.732x0.5 = 1391 amps
can the transformer winding take this amount of current.You see on both occasions the load was 500 kw but the pf was different and the amps was double.What will happen if the transformer is loaded at a further lower pf. should the transformer be still rated as 500kw
| Is This Answer Correct ? | 4 Yes | 9 No |
Post New Answer View All Answers
why did youi choose this career?
what is the soft starter principle? how is connection diagram? what is the procedure for checking the connection?
Explain difference between stand by earth fault and residual earth fault protection?
how u select control transformer for a mccb panels or any panels?for expample we hav 440 volts maim supply and control volts is 230v?
how can maintain the power factor and why and this is how do work tell us
Difference between RCCB, RCBO and ELMCB.
WHAT ARE THE CHARACTERISTICS OF AN VOLTAG AMPLIFIER
What is meant by Load Encroachment in OHL Feeder Protection?
Can anybody please refer the best and simple book for about Protection relays and in detail of all its protection ?
What do you mean by a voltage transformer?
what is the use of power transformer in GSS.
Which contains in POLE ASSEMBLY of a 11KV Kirloskar-make SF6 (Model No-FP620A12)? Will u clarify with drawing?
Why the efficiency of a three-phase induction is the motor is less than that of a three-phase transformer?
hi friends if you have any 400KV Substation Erection and installations Drgs please send to me.My email id:kandi.suresh441@gmail.com
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?