i heard that power factor(PF) is the main concern for
industries, if they are maintaining PF around 0.6 they will
be fined for that. now the question is, how can they improve
the PF ranging between 0.9 to 0.95 which is safe for them
i,e escaping from the fine?
Answer Posted / pillay
The PF is low because of inductive load. You can improve IT by adding capacitive load. Luckily cap load is loss free.That means you dont pay kwh for it but you must buy and maintain the capacitor and on and off it as necessary at the right amount.
One way to know how much you need, is you must know the load in KW and the pf.
assuming the load is 500 kw and the PF is 0.6 and you want to improve it to 0.95. you can find out the kva demands at this two pf levels
500/0.6=833kva . 500/0.95=526 kva, 833 kva -526kva =307kva
If you add 307kvar into the system in paralel you would improve the pf to 0.95 you can divide this into 8 steps of 40 KVAR each connected accros the 3 phases through an auto PF regulator.Your cap on each step will be rated as 40 kvar at 415 volts (rated voltage) 3 PHASE.
I welcome any improvements or comment about this.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
how to protect motor in dol starter having capacity of 30 hp.40 hp?
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
what is working process of star delta controlling circuit ?
What is dynamo function in DG sets and draw block diagram?
wat is d diffr btw shunt coil and trip coil in VCB?
How many kinds of E.L.C.B and how to work E.L.C.B
HOW TO CALCULATE THE HEAT AND LOAD OF LT-SUBSTATION WHICH CONTAINS 2*1MVA TRANSFORMERS,LT SWITCH BOARD,MLDB,ACB,BUSBAR,ETC...?
What happens when ac supply is given as excitation voltage instead of dc supply
What is notching in dc machine?
why the protection turbo generators is most complex?
what is the need of starter in tube light and what type of starter is used in that?
How can eliminate noise problem inside temperature controller temp. variation due to contactor chattering problem.
for what purpose the star point is done in ct
In how we connect watt meter for open & short circuit test of a single phase transformer.