after parallaing two generators current is shooting up in
both the generators.for ex: load is 400 kw..after paralling
and load sharing current in running gen is approx 900 amps
and incoming is 750 amps which is too high when trying
toshift the load current in incoming gen is coming more
than 1300 amps and both getting tripped and making
blackout..
Answer Posted / pillay
it looks like one of the genset is having a big difference in voltage or
the droop kit if fitted something wrong with it or
check after paralling do you have balanced three phase voltage and current or one of the phase is open circuit or
the gen is running the other as motor
if you know the actual reasons later please let us know also
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
I Just want do EHS Certified Certification Distance Course From Govt approved,so can any body provide me details.
can i connect the two phases of scott connected transformer,if not why?
what is the reason for indication of light in the earth lamps of main switchboard.if there is an earth why does one lamp get dim and the other two bright.
When are the directional relays used?
PLZ EXPLAIN CORONA,SKIN,BIRD PALE,SPAN,SAG Effects of power cable.
where lt & ht capacitor used
what is mean by PIR in circuitbreaker and give me detail of that?
How to calculate the fuse rating depend upon the DC circuit?
The capacitive reactance of a capacitor of 1/(2(PI)) F at 10^3 H is
Can anybody tell abt concrete encased earthing or grounding?
How can we measure the residual voltage in dc machines?
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
What is the simplest formula to calculate the rotor diameter of a synchronous generator?
is it possible to start a motor in felid connected to a remote mcc
WHAT ARE THE DATAS REQUIRED FOR PROTECTION AND METERING AND CONTROL AND LOGIC PREPARATION,HOW TO STUDY THE PROTECTION AND METERING?