why we use to transmit the power in three phases intead of
single phase ?
Answer Posted / gunasekaran
power loss will more in single phase than 3 phase for
example we have to transmit 100A current for single phase
system .
2*Isqr*R= 2*10000*R=20000Rwatts
for 3 phase system 3*Isqr*R=3*57.7sqr*R=10000R watts power
has dissipated so 3 phase system better than 1phase
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
In the N-series schneider reclosers. What is the difference between current during fault time and current at tripping? This appears in the Event log in an event of a trip out.
I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?
What are the application of filter?
Can u explain : what is supply for train (whether a,c or d.c ).I know that supply is 25000v a.c .But there is rumour that supply is D.C. And also explain how lights and fans inside the trains are working ,and what type of motors are used in trains whether D.C motors or induction motors .If d.c motor, how it gets supply.If traction motors are used then what are traction motors and its functions and how it differs from other motors and also explain about locomotive . y d.c series motor in train.train wheels r driven by D.C shunt motor ,at what voltage,and at what speed. please reply..............
Hi.. I am a BE GRaduate in E&E. I have 8.5 Experience in Tendering & Estimation field. I have done SAP SD course few years back. But due to some reason i failed to get job in that field and continued my own field. Now I am thinking of changing into SAP seriously. How should i go ahead???
Define filter?
Inverter. converter. Ups.MCB.solar.alternators. motors.
Why L.T.Cable voltage rating is 1.1kV,where as system voltage is 0.415kV?
Differentiate between real and apparent power?
How to Calculate the Fault Level of Electrical Installation
what is spadar bar .why I use in DC generator.
what are the dimensions for 200 kva transformer plinth (plateform),in which pcc m20 is used..
how to discharge 3 phase power factor correction capacitors
What is the formula to calculate the size of Aluminium and copper cable?
why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?