for testing busbar (33kv) hi-pot .whether we can apply DC r
not.and what is the test volt for that .explain
Answer Posted / vijay
Yes, we can.
For test voltage we have to apply 80% of factory test
voltage i.e. 80% of 70 kv ac (factory test voltage) =56 kv
for 1 min.
| Is This Answer Correct ? | 11 Yes | 6 No |
Post New Answer View All Answers
What are the advantages and disadvantages of the ac motors?
Wind mill
What is a fuse? How does it work? What are materials used?
can i connect REF and Differencial relay in 1 CT core for transformer protection?
I want to know how to calculate the size of electricity cable in building?
Why r u using pf panel. what the uses
why Induction Generators are not "Black start" ? and apart from WTGs where this types of generator are generally used?
why the perameters of secondary circuit are more important then that of the primary circuit of induction motor?
How to convert a two phase power into a three phase power in induction machine?
what is high - pot test. what's its use?????
Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control
CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS
what is the defination of Cable database? What are the points are considered while preparing cable database? Is there any sample available for cable database?
Is there chopping current in resistive circuit
What is the Temperature to be set in Thermostat provided in Marshalling box of the Transformer / Motor.