Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to choose the cable rating for load (KW)? EXAMPLE.50KW load

Answer Posted / engineer

Right cable size Sellection depends on 3 factors:
1- Load Current.current(I) = 50kW /(1.732*415*0.85
(p.f)) =139A

2- Distance(From feeder to your load)
3- Allawable Voltage droop in your system (Should be less
than 5% )

As experience you can use 10sqrmm for 40A,for 120meter.

Is This Answer Correct ?    117 Yes 52 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is p.s impedance measurement test in earthing transformer?

2345


how to compute kAIC?  with formulas...

4183


Write the force balance equation of m ideal mass element.

1181


dg earth connect only in the amf panel or not why

2018


In an ACB shunt trip coil and undervoltage coil operated normally( breaker open and charged). But closing coil not operating untill manually discharge and recharging. Any help.

1699


What is the use of mc( moving coil) in dc voltmeter and dc ammter and what is the use of ( moving iron)in ac voltmeter nd ac ammeter

2843


How to test REF relay testing for LV panel as per Kahramaa standard?

4879


why do we carry out winding resistance test?

2223


What does the letter CTNM in negative phase sequence relay means?

1740


How many double suspension hardware fittings are required on a double circuit transmission tower?

1876


What is the function of NER and NET?

2398


a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn

1489


What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?

1974


What is the requirement of grounding the neutral of single phase generators on load? If the neutral is not grounded, what will be the effect?

2063


CAN U PLEASE TELL ME SOME G.D TOPICS FOR APGENCO INTERVIEW&G.D

2353