Why not implimenting power factor in Diesel generator
Answer Posted / ravi
In case we correct the existing P.F. in case of DG set by
putting capacitor panel across DG set, then there is no
harm until the cicuit draws inductive or lagging P.F. . But
in case it starts drawing leading P.F. due to addition of
excessive capacitors across D.G. set then the output
terminal voltage would be higher than the induced voltage.
so it is not desirable to operate cap. panel across DG set.
Is This Answer Correct ? | 8 Yes | 1 No |
Post New Answer View All Answers
What is synchro?
Can we test the alignment of End shield and stator of turbogenerator without rotor insertion? Also how to fix maintain the alignment at site installation?
1.main parts of generator? what is used A-check,B-check,C- check? 2.what is FM200 system in data centers? 3.difference between pac,ahu?
Dear sir, By which formula u can calculate for a particular kv line there is a range of mw.
how oltc works in rectiformers of higher rating (27 mva,200v dc,120kamps) please provide me full information with diaggram.
WHAT IS SUBSTATION & ACCORDING TO VOLTAGE HT,EHT SUBSTATION EXPLAIN IT
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
I have c license but I don't know eligibility of Max Kilo Volts under the electrical licensing board.
what is high - pot test. what's its use?????
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB
ht side line to earth voltage
How the capacitance og capacitor volatage transformer is decided?
What is the exact formula for one weber of magnetic flux?
what is the difference between Power and Distribution transformers ?
33kv substation lay out details & line to line & line to earth measurements