Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

For Synchronisation of DG Sets Sometimes we people use NIC
(Neutral Isolation Contactor) Instead of 4-pole ACB or any
switchgerar..Please guide me why is it so????

Answer Posted / srikanth shreenidhi

Whenever DGs are paralled & synchronised one should have a
common neutral.If neutral of one generator fails
automatically the neutral of other dg sets which is on a
common bus takes over.Whereas if the DG has a 4 pole
breaker and neutral fails it will be impossible for the
system to continue as all the dg sets will have a switched
neutral.
Secondly in case of neutral/contactor failure the user will
have to change only the contactor instead of the whole
breaker

However when only one DG set is used we always go with 4
pole breaker.

Is This Answer Correct ?    16 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

hr round

2108


How wire size can define in electrical wiring? What is the ratio?

2275


What are protections for dty type transformers

1806


1) why a dg set shows variation of power factor and load when synchronised with other dgs? 2)Why the load sharing is not become equal in all dgs?. 3)When a dg set will not run on auto start?

1984


how to setting Load amps tripping time and extra settings for load Transformer protection relay with RMU panel using C&S model relay..?

1118


what is KA rating and how can we choose switchgears on applications

1427


What is dielectric loss?

1120


what is a vector protection in transformer

2001


DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.

1949


How to know Resistance and Reactance value of main and aux winding of single phase capacitor start capacitor run induction motor to find capacitor value?

2032


What happen Grid EARTH plat got cut.

2207


what are the condition that makes hooter blow?

2427


Why does amplifier gain reduce?

1036


Why is remote backup preferred to local backup?

2050


full form of electrical?

2697