For Synchronisation of DG Sets Sometimes we people use NIC
(Neutral Isolation Contactor) Instead of 4-pole ACB or any
switchgerar..Please guide me why is it so????
Answer Posted / srikanth shreenidhi
Whenever DGs are paralled & synchronised one should have a
common neutral.If neutral of one generator fails
automatically the neutral of other dg sets which is on a
common bus takes over.Whereas if the DG has a 4 pole
breaker and neutral fails it will be impossible for the
system to continue as all the dg sets will have a switched
neutral.
Secondly in case of neutral/contactor failure the user will
have to change only the contactor instead of the whole
breaker
However when only one DG set is used we always go with 4
pole breaker.
| Is This Answer Correct ? | 16 Yes | 8 No |
Post New Answer View All Answers
what the Microsoft .NET framework is?
Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..
explain comutator action in detail.thanks
What are the electrical engineer roles and responsibilities in chemical plant?
How many lightning arrestors to be installed on 50MX60MX10M building and is there any formular for that?
List out the different frequency domain specifications?
what is the significance of tan&delta and how it performed in power transformer
What are PLC leader logic program method
raleigh method
what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing
What are the effects of electrical faults?
What is the Nyquist criterion regarding control systems?
What is the drawback of class b amplifier? How is this minimized?
I WANT YHE TECHNICAL AND ELECTRICAL SPECIFICATIONS OF 2x4MW 11KV 2x10MW 11KV 2x25MW 11KV 2x100MW 11KV HYDEL POWER PLANT i.e PROTECTION SYSTEM,MONITORING,CONTROL SYSTEM,GENERATION,SYNCHRONISATION,METERING PLEASE SEND THE DETAILS TO MY MAIL ID SPRAVEEN_222@YAHOO.CO.IN
suri transmission