can we load Power capicitors on DG sets?
Answer Posted / amarnath
YES ! The DG Rating is always defined in KVA @ 0.8 Pf Lag.
Hence for optimum utilization of the DG power, it will be
best to have the PF regulated to 0.8 PF Lag. However, care
must be taken not to let the PF go into LEAD condition as it
can lead to instabilty of the system voltage. Suggest to
conduct a detailed load study and opt for Automatic PF
Improvement Relay panels wherein the DG target PF can be set
@ 0.8 and for EB the target setting can be 0.95 Lag or above
. (definitely not LEAD)
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
When semiconductor fuse does save thyristor in each cycle of conduction? Why under voltage setting keep less in SPRS and more in DC drive?
I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
What is the permissable nutral current of three phase system as per IS standards?
what is class of SPD and dittels of all class ?
upto how many load can v connect to stabilizer which is used for tv
What is the differentional relay...what is the work of this in power Tx. how it is works..
What do you understand by external characteristics of a d.c. Generator?
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
What are the different power system losses and how can it be eliminated?
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
What are the types of excitation system?
Why delta star trformers are used for lighting loads?
how to test power transformer.YNd11
how can we calculate the ampacity of the electrical wire/cable. and what are the factors must be considered. pls. elaborate.