what will hapen if secodery circuit is open of current
transformer
Answer Posted / thowsif_emerson_csm team
The CT Will Burn....
Why does opening a CT's secondary cause dangerously high
secondary voltage?
With the flow of both primary and secondary currents the
transformer's exciting current is very low. The secondary
current mmf serves to keep the magnetizing flux in check!
If the secondary now opens the primary current mmf produces
an exciting current 'orders of magnitude' greater than
normal. And, the resultant large increase in flux density
produces an extremely high voltage in the secondary.
Regards,
Thowsif.
Is This Answer Correct ? | 26 Yes | 3 No |
Post New Answer View All Answers
a governer in an Ic engine controls the
What is knee point voltage of transformer?
sir i want previous entrance exam papers for written test
We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.
In India the supply voltage is 230 volt A.C. During the negative half cycle phase becomes neutral and neutral become phase? or what will happen during negative half cycle? how the electrons flow during positive and negative half cycle?
i am completed in B.E(Electrical and Electronics Engineering) with 8 months experience in Quality Control Engineer at Bharathi Industries,Coimbatore.
How do we calculate over and under frequency tolerance from generator data?
What is the tension required for the 25000 CFM AHU belt
what is capacitor voltage transformer?? how it is different from potential transformer?
what is difference between earthingpits,earthing grid & earthing mess?
(1)Can earth and be conected together (2) what is the diferent between earth & neutral
what is 30-phase of transformer
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
why to use freewheeling diode ( diode in revers bias mode) across dc coil