what will hapen if secodery circuit is open of current
transformer
Answer Posted / thowsif_emerson_csm team
The CT Will Burn....
Why does opening a CT's secondary cause dangerously high
secondary voltage?
With the flow of both primary and secondary currents the
transformer's exciting current is very low. The secondary
current mmf serves to keep the magnetizing flux in check!
If the secondary now opens the primary current mmf produces
an exciting current 'orders of magnitude' greater than
normal. And, the resultant large increase in flux density
produces an extremely high voltage in the secondary.
Regards,
Thowsif.
| Is This Answer Correct ? | 26 Yes | 3 No |
Post New Answer View All Answers
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.
As per the Anchor capstan motor specification, full load current is 200A. starting current is 1750 A and acceleration time is less than 8 seconds. Please guide for selection of cable size.
How does an oscillator differ from an amplifier?
what are the accessories need to be added while doing estimation for the following: 1.MCCB 2.MCB 3.ACB
how to test power transformer.YNd11
10 Mtr Hight of Lighting Arrestar how much area coverd??
What is the basis for framing the rules of block diagram reduction technique?
How to calculate cable size in HT AND LT
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
when will be the iocl interview results ifaced the interview on september 8 th
What is the difference between isolators and electrical circuit breakers? What is bus-bar?
If a air condition consume 2.50 to 3.00 amp then how much it will consume in watts if it is running 10 hours out of 24 hours????
i karmveer bharti persuing b.tech . plz send me syllabus and name of reference books. for preparation of section eng.
how is the connection of a 3 phase ct trivector meter done on a pole mounted transformer
After taking shutdown of 11kv feeder, if you see 5kv by phasing stick in the cable side, is it possible to close earth switch in cable.