when the operation engineer told you that he gives the
control valve order to open but there is no response !
what will you do ?
and if you found that there is astuck , what will you do ?
(note : it is apanumatic valve )
Answer Posted / chitturi bhaskara rao
1.First measure 4-20mA in field side if cannot get 4-20
then check AO card , if u got 4-20 in field side then check
positioner ,
2. make sure thatt sufficent air supply i,e 3 to 4 bar at
inlet of positinoer.
3.If all correct still valve nvr moves then remove
positionner from the valve and supply the air directly to
actuator ( to 4 bar max) then valve moves smoothly then
check angle of postioner while ur fixing positoner on
control valve .
4 if valve nvr moves smoothly means in side valve jam need
to send over haul
| Is This Answer Correct ? | 20 Yes | 0 No |
Post New Answer View All Answers
how to commission furnace ( water heater)
what about your moleg in pogrees with company
what is the calibration procedure for transweigh make weigh feeder?
what happen if i increase height of displacer type LT.accuracy or sensitivity are affected.why?
how u choose thermowell lenght n pnumatic C/v size?
Explain the working of an enraf level gauge.
what is exact time to study dcs and plc cources
What is instrumentation technologists and mechanics?
find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s
line up procedure for dp type flow transmitter?
can you provide me full detail about instrumentation in ONGC??
how to calibrate steam control valve in steam turbine
what is cems analyzer explain with principle and drawing ?
how many type of plug are used in pneumatic control valve,name them.
Explain the working of rota meter.