What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.
Answer Posted / thowsif_emerson_csm team
For 300 KVA the Full load Current=KVA*PF,
i.e 300x.8=240000 Watts.
we know in 3 Phase Circuits,
P=1.732x V x I x Pf,
I=P/1.732xV x Pf,
I=240000/1.732 X 440 X 0.8,
Full Load Current, I =240000/609=394 Amps,
The Load Current @ 40% is 394*.40=158 A(Total Load Current).
The Load Current @ 45% is 394*.45=177 A(Total Load Current).
So load current at 40% Load is 39*.40=15.6 A/Phase Amps.
| Is This Answer Correct ? | 11 Yes | 6 No |
Post New Answer View All Answers
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
why the difference arise between HT reading & LT reading (submeters fixed in complexes, apartments etc)if the power factos exceed from 0.9 to 1 can the ht meter reads fast?
What the difference between ac and dc inductor an capacitor
What are the causes of unbalanced current on 34.5kv feeder Ia=0.05,Ib= 0.25, Ic=0.15 and In=0.27 prior to tripping current are balance?
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?
define reflection method?
What are your future plans for the company if permanently employed?
on a three-winding transformer relationship delta-delta-star, on third winding why the relationship is a star? what are the advantages and disadvantages? Thank you and please help
what is the constructional difference between a power transformer and potentian transformer?
how to calculate magnetic force genrated by a coil ?
What do you mean by a current transformer?
what is the synchronous timer ? and it applications.
1.what is the reason for transformer and lightning arrester blast in 33kv system
Keywords: Die, Card, Coin, B/N 2 To 12