plz explain TSM and PSM.with example suppose ct ratio is
4000/5 and tsm is .15 and plug is at 3.75 if fault current
is 8000A.so how i find relay oprating time.
Answer Posted / yashpal
plug setting is = 3.75 means pick up= 3.75 A.Relay
operating time will depends on the charecteristic of relay.
(invese,normal inverse).if the fault current is 8000A then
current in the sec will be 10 A which is three times of
3.75A(connected plug setting),now just watch the relay
charteristic written on relay u can get the time required
for relay operation.(ex- for inverse charecteristic relay
for 3 time current & tms = 1 ,timing is 6.25 sec,so for
our problem timing will be 6.25 * 0.15=0.9375 sec.
| Is This Answer Correct ? | 16 Yes | 5 No |
Post New Answer View All Answers
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
What is 100% protection of generator? Why 100% is not used but 95% is generally used?
What is voltage divider rule?
Why computer humming sound occurred in ht transmission line?
what is the most permissible winding temp when we conducting a generator load test?(condition no load)
What is bridge rectifier and explain with details
Explain about Leakage Test.
how ct burden,magnetising current,ratio and knee point voltage are related & derived
What happens if i apply 500V to 440V rotary Switch ?
what is the difference between Power and Distribution transformers ?
how the aircraft outer body and inner body is separated ?
Why in power plant projects we see DOL starting method used for motors upto 160 kW instead of star delta method
At what speed an electric car can run with 2 HP motor of weighing 400 kg?
What is the use of lag compensator?
what is the difference between RMS & TRUE RMS VOLTAGE