6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / loke
We can agree with Mr.Mnm because actually the rating of
breaker ia 690v and it will be having with stand capacity of
+_10% so it can with stand upto 765v & also check out with
the impedence it would be around 6-9% from that also you can
check secondary voltage of t/f.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
one conductor length is L.and i am strech uniformly this conductor and made length is 2L.so resistance of this strech conductor is R=4R..but i want to know about area of stech conductor hows it become a/2..
How to address the servo drive for motor
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
diff. between tension mode & speed mode
What is order of the system?
What is the effect of solar radiation on the design of an Isolated Phase Busduct?
WHAT IS SITTING AMPS IN OVER-LOAD RELAY FOR 1PH OR 3PH MOTORS?IF ITS NAME PLATE GIVEN MAX AMPS 10AMPS?
what is the difference between capacitive and resistive voltage divider?
why we are using Load factor?
what parameters are should nessary for control technic dc drive(in rolling mills)?
What is meaning of out of phase (making & breaking) capacity And how to calculate
What is the difference between resistance grounding system and resistance earthing system?
What the difference between three phase contactor (coil 110vac) & three phase SSR (control voltage 110Vac)? May I use contactor in place of SSR?
How a capacitor discharge weld power supply works? what is the use of a pulse transformer?