A motor works on 30 killo watts.how much ampers will be
required if it works on 440volts?
Answer Posted / irfan ahmad
V=440 V
P=30 Kw = 30000 w
we know that ,
P=1.732VI*(power factor)
I=30000/(1.732*440*0.9)
I=43.7 amps [power factor in application is 0.9]
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
Write the analogous electrical elements in force voltage analogy for the elements of mechanical translational system.
how was your last weekend.
What is the HVDC Transmission System? What are the conditions applicable to lay an HVDC Line?
What is the exact minimum vale of voltage between an earth and netural which can damage or can do malfunction of the electronic equipments ? If this is mentioned in any book, pl.give reference.
Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.
why do we use 25kv supply for traction purpose?
why use phase displacement in transformer.and effect of phase displacement on transformer
What is the use of bundle conductors?
why +24 v and -48 v give to BTS? If -48v protect from surge then why we not use -24 v?
how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
Please send 110 kv sb station full single line drawing(sld)
Will an earth leakage trip be activated if the component or wiring is faulty on low voltage equipment.Example An electrical Cat Scarer placed in the garden and water gets into the wiring.
State kirchoff current law?