Answer Posted / anand
Load Current= KW / 1.732 x Line Voltage x P.F
= 30000 / 1.732 x 440 x 0.7
= 56.28
= 56 A
Note:
Power factor of Inductive(Motor)load: 0.7
| Is This Answer Correct ? | 8 Yes | 2 No |
Post New Answer View All Answers
WHAT IS DIFFERENCE BETWEEN MANUAL CONTROL AND MAGNETIC CONTROL AND STATE ITS ADVANTAGE /DISADVANTAGE
we have provided 30 nos. relay contacts in panel.I want to know how do we do the numbering for the relay contacts as per any applicable standards
why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points
errection check list for transformer maintenance
why need to be maintain power factor for industrial customer?
Dear all, I just want to ask an expert on this forum for some insights. For the magnetic balance test, when applied voltage on a Delta-Star transformer e.g. Dyn11, the following relationships apply for HV side: 1. H1-H2 = H2-H3 H3-H1 2. H2-H3 = H3-H1 H1-H2 3. H3-H1 = H1-H2 H2-H3 For the LV side also: 4. X1-X0 = X2-X0 X3-X0 5. X2-X0 = X3-X0 X1-X0 6. X3-X0 = X1-X0 X2-X0 Is there a similar pattern for Y-d, Y-Y, D-d? And how about Y-z, D-z, Z-y transformers? I've tested a YNzn5 transformer and for LV side I don't see the pattern. In this particular case I got for LV side the following (see values below): H1-H0 H2-H0 H3-H0 X0-X1 X0-X2 X0-X3 128.0 119.9 7.2 29.2 13.3 15.8 70.7 128.4 59.2 23.4 22.0 3.6 7.2 120.1 128.1 13.4 29.3 15.8 What is the relationship here for LV? For row 1 I see the relationship, for row 3 I also see but it's shifted, but for row 2 I don't see such relationship. Any suggestions, answers, someone?
how to wiring it with contactor and timer together
What is the need for a controller?
What is maximum power transfer theorem?
How to Calculate The sag of OPGW in Transmission Line???
Pl. share your experience about industrial-electronics repair of machine tool.
what is meant by IGBT how they differ from tyristor ?
at which voltage level arcing ground is occurs ??????????
which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?
does the Trivector Meter of three phase automatically takes care of the low power factor and gives the reading accordigly or it does not take care of the Power factor while giving the readings please explain