i have 28/32 MVA power transformer with 11/6.6 KC voltage
rating and 12%impedance.it have star connection at both
side.but it have another thied winding tertiary
winding.what is used of this winding.
pl tell me
Answer Posted / engr. l. o. osuji
Hi Paliwalsureshi,
Makers of such transformers usually provide a tertiary
winding connected in delta. This winding is sometimes called
compensating winding. As others have rightly said this
winding help to eliminate the harmoics which may interfer
with communication in power system. Before the advent of
microprocessor-based differential relays the old
differential scheme with star-star on one must have a delta
winging in between.In a nutshell any star-star connection
must have a delta tertiary.
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
when will be the iocl interview results ifaced the interview on september 8 th
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
what is a reactive power? what is the relation with power factor?
Advantages/Disadvantages of earthing of neutral bus on MSB instead of separate neutral earthing for transformer/DG sets feeding to MSB
what will happen if the prime mover on the field excitation of the on-coming generator fails?Explain.
sir am giving jspl exam on 19th oct . i belong to eee, so plz send previous question papers ..........to dis id abhilash203@gmail.com
For the requirement of a furnace of temperature range up to 1200 oC using silicon carbide rods, What is the required rate of transformer needed (please do it with all details)?
What is the bundle conductor?
Best way to measure the Soil resistance of rocky soil, three probe method and four probe method
Can we convert off line transformer to on line transformer
how to calculate the size of the HT cable
Why power genaration in India is at 50HZ while America its 60HZ
HOW TO DESIGN THE body EARTH cable(Copper Conductor) size for 60KVA UPS?
what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?