We have 2 no. 4MW DG set. and GEB supply.
But, we running, only 1 DG set. when we done APFC/Power
factor setting : 0.90, then winding temp. Low. but when
setting done : 0.83, then Winding temp. increase.
WHY Why ? ? ?, plz give me answer.
Answer Posted / gurucharan singh
this is clear that at lower pf settings, its the DG which
compensate for the KVAR. which results in the high winding
temperature. For this check the plant loads connected. And
KVAR supplied by EB & DG. Also during parallel with grid DG
generally act as KVAR compensator along with KW supplied.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
WHY BLADE & JOW OF ISOLETOR IN SUBSTATION?
How to select the cable and voltage drop in circuit?
Single line diagrams for star to delta and DOL starters.
How to know th details about an electrical Drawing ? Please mention the easy method.
what is the importance of Partial Dischage test for Electrical Equipments
What is a surge supressor why its is used in synchronous generators
Why does amplifier gain reduce?
How many kinds of E.L.C.B and how to work E.L.C.B
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
1. for eg, capacitor is used for many purposes(it act as filter, oscillator, bypass capacitor, memory storage etc...) 2. Please tell me some example circuits for different uses of capacitor( whenever and whereever and however we used capacitor as a filter, oscillator tuning etc..) 3. similarly for inductor and resistors(it act as what?) and when and how we want to act as like that?, and how we can used these components depends upon our requirments with example circuits and explanation? design to act as these components depends
what is the function of impulse relay
Transformer how to maintaince a check b check c check d check
In 11/0.414 KV Parralel supply network with Bus tie closed what will be the fault level is it doubled or halved??
what is difference between isolation and ultra isolation transformer?, what is the method of testing ?
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.