Answer Posted / y.rama krishna
Connect 1U&2U
Apply 3ph 415V balanced voltage across terminals 1U,1V,1W
(HV wdg)
Measure the voltages between the given terminals & record
1)1U-1V
2)1V-1W
3)1W-1V
4)1V-2V
5)1V-2W
6)1W-2V
7)1W-2W
8)1U-2N
9)1V-2N
Verify the conditions
a)1W-2W = 1W-2V
b)1V-2W = 1V-2V
c)1U-1V = (1U-2N)+(1V-2N)
vector group Dyn1 confirmed if the above conditions are
satisfied.
| Is This Answer Correct ? | 18 Yes | 16 No |
Post New Answer View All Answers
How to perform a DC resistance test In Alternator and their proceduces?
When steam condenses and becomes water at the same temperature, the specific heat for the process in kJ/kg k is
If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?
How maesure earth neutral value & how much maximum value value required in between earth & neutral.
Purpose of providing neutral isolation panel for parallel operation of diesel generator
what is the difference between transformer,converter and transducer
What are the two basic types of transformers?
What is the main purpose of c.f.b.c.boiler
why we not used 11kva as a direct our electrnics component.
How shall i select the value of capacitor or inductor in a system?
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB
What is an automatic controller?
In our plant we have installed new MCC with ELR and CBCT which is detecting some leakage current in the system but it leading to some confusion when to check that in which feeder which is drawing current we put off the whole panel itself but still CBCT detecting some leakage current so can anybody ans me , where i am going wrong or how to detect whether its actual leakage or CBCT malfunctioning.
what is the purpose of using filters in a protective relaying scheme?
What is deference between MCB & MCCB & ISOLATOR