without any theoretical calculations, can u approximately
tell the current rating of a motor(above 30hp)working at 415VAC.
Answer Posted / azarudeen
Above 40A (if efficiency of motor - 90% & PF - .8)
FORMULA: I = (HP*746)/(1.732*415*Eff*PF)
| Is This Answer Correct ? | 4 Yes | 3 No |
Post New Answer View All Answers
Is there any reason that we get shock on touching phase wire because the earth is at neutral potential? Is there any reason that the earth is at neutral potential because the neutral is earthed in apower station
why Lightning arrestor are made by 2 seperate stack of inslutor but why cvt are in single stack of insulator.
working of diesel generator ?
What is mean by Sensitive Earth fault & what are the effects
How are load losses and no-load losses measured at site in a DG set?
why should small green grass ans small plant should not be there inside the transformer Yard in the factories
For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?
Is it possible to connect a safety device in to parallel?
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
What are the two major types of control system?
What is Primary And Secondary Injection Test of Relay and Other Electrical Devices. How IT is carried out.
why high speed tripping relay is used in protection circuit why not normal relay
what does a k rating in a transformer means?
Please explain, how to test vector group of tranformer(Delta y1) . Thank
how to increase senstivity of ct