How Much Capacity of Diesel Genset is suitable for
20 no.s of 1.5ton AC's & Why?(Load Calculation)
Answer Posted / girijapati mishra
TOTAL REF LOAD =1.5X20 =30 TR
1 TR = 3.5 KW
Thus , 30 TR = 105 KW
COP (i.e ratio of heat removed vs power input ) for AC
varies from 2.5 to 3 depending on design and other
considerations.
Assuming a COP 2.5 ( lower side)
Power required will be 42 kw (=105/2.5).
Considering power factor 0.8 ( gen assumption for all
caculations) rating of the DG set will be 52.5kva ( =42/0.8)
. A DG set higher than this calculated value to to selected
for this requirement.
Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers
how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???
Define early construction of human being
what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing
What are the different circuits in thermal power plant?
I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.
1.what is difference in maintain Hz again Hz in USA ? 2.how to calculate the battery AH? 3.why are yearly maintained in transformer how many tests in required?
why incomer bay is required before transformer bay if there are more than 1 nos. of transformer bay.
What is minimum phase system?
how to size H.T & L.T Panel ?
What happen to the transformer if the OLTC frequently used for lower and raise occured 50times daily?
Single line diagram for dbb (double bus bar)system.
What is the difference between a verilog task and verilog function?
What is meant by analogous system?
What is the source of dependent source ?
which pump used in STP