How Much Capacity of Diesel Genset is suitable for
20 no.s of 1.5ton AC's & Why?(Load Calculation)
Answer Posted / girijapati mishra
TOTAL REF LOAD =1.5X20 =30 TR
1 TR = 3.5 KW
Thus , 30 TR = 105 KW
COP (i.e ratio of heat removed vs power input ) for AC
varies from 2.5 to 3 depending on design and other
considerations.
Assuming a COP 2.5 ( lower side)
Power required will be 42 kw (=105/2.5).
Considering power factor 0.8 ( gen assumption for all
caculations) rating of the DG set will be 52.5kva ( =42/0.8)
. A DG set higher than this calculated value to to selected
for this requirement.
| Is This Answer Correct ? | 7 Yes | 2 No |
Post New Answer View All Answers
How can we choose the rating of submersible motors
how can i get the formula to find out the cable size if i know the load of main fuse protection.
What is the difference between vector surge relay (78) and Pole slip relay (98G)
Vibromotor 252MV 1/4HP2P..what is mean by 252MV?
Pls explan the OLR setting in VCB at HT yard
if any body have question paper of railway (section engineering),then plz send me .i will thank of him/her.
What is the capacity of the Fastners 12mm?
Good morning: I'm looking for some informations about the OLTC or the LTC: I wont to know what the function of the tie-resistor in during the operation of reversing/coarse operation Cordially
I want to know all basics of electrical engineering
1.main parts of generator? what is used A-check,B-check,C- check? 2.what is FM200 system in data centers? 3.difference between pac,ahu?
how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
how we findout a ignater is faulty or not?
how to revers the direction of single phase motor
What is kvar?