For a Potential Transformer(PT), the primary neutral
terminal must be grounded before energization. Why....?
What will be heppend if we energize the PT without grounded
the primary neutral point? Why..........?
Answer Posted / om s.
while connecting pt each primary phase winding is connected to phase to earth. The neutral point of load is connected to neutral point of secondary’s. Neutral point of primary is solidly earthed.
If primary neutral is not earthed the zero sequence component of voltages (due to earth fault) cannot flow through primary windings. Hence phase to earth voltages of system which contain zero sequence component do not get truly transformed and measured voltage are distorted. Hence the earth fault on system cannot be sensed on secondary side of VT.
| Is This Answer Correct ? | 22 Yes | 2 No |
Post New Answer View All Answers
How do u analyse protection fault when vcb tripping on load
what is the difference between surge protection capacitor and surge arrestor
how to calculate short circuit current for the busbar
What is safety of Ht panel
What is the technical difference between On delay timer and a Star delta timer?
please forward me the type of questions which would rise while me attending to 33KV Electrical License to my mail ID:vadrevu_raghava@yahoo.co.in
do you have some of interview Questions in power and genrator section in general whith answers
What are :- AC Distribution Board (Single & Double Front) DC Distribution Boards Distribution Board LT Breaker Panel.
What is an order of a system.
completed BE & done apprentice at tneb & having experience 6 years. want to get c license. will apprentiship & BE be helpful for getting c license. will i get any preference by showing this?
What are the specifications for getting approval of Substation?
Motor,transformers,capacitor tubelight etc....
how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.
The knee point of a current transformer is normally unique and known.So why in the nameplate of a CT they put the minimum value like this Vk> 400v.
how could we calculate the no of outgoings from a 800 watt distribution board