For a Potential Transformer(PT), the primary neutral
terminal must be grounded before energization. Why....?
What will be heppend if we energize the PT without grounded
the primary neutral point? Why..........?
Answer Posted / om s.
while connecting pt each primary phase winding is connected to phase to earth. The neutral point of load is connected to neutral point of secondary’s. Neutral point of primary is solidly earthed.
If primary neutral is not earthed the zero sequence component of voltages (due to earth fault) cannot flow through primary windings. Hence phase to earth voltages of system which contain zero sequence component do not get truly transformed and measured voltage are distorted. Hence the earth fault on system cannot be sensed on secondary side of VT.
Is This Answer Correct ? | 22 Yes | 2 No |
Post New Answer View All Answers
please explain how to do 'pole drop test' on generator?
what is diff btw electric,magnetic & eletromagnetic field
HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?
Define what is the function of anti-pumping in circuit breaker?
what is POTT and PUTT explain?
how to measure the current by compact digital equipment with dislay which fit inside any equipment
what is sevice settings for mccb?How can be it setted?
how to calculate the fault in substation
how freewheeling diode improves the powerfactor
What is installed in PAC that is control the humidity
How to calculate loses in transformer of 160 KVA ?
can i use 4 number of circuit breaker as single phase manual change over switch? if yes then how plz also send ckt diagram at nazimzamurad@gmail.com
What are the temperature elements?
What are the basic elements used for modeling mechanical rotational system?
What are all present producing cost of Per KWH of various Fuel?