what happen if i connect DYn11 and DYn1 vector group
transformer in parrallel?other things are same like votage
ration,x/r ratiob etc...
Answer Posted / salah
Dyn11-secondary voltage lags primary by 30degree
Dyn1-secondary voltage leads primary by 30deg
hence it is not satisfying the condition for
pare;;alisation .
if we connect two TR in parallel current drwn form the
source by both transformer is not in phase hence
circulating current will produce & damage the winding as
well in secondary aslo
| Is This Answer Correct ? | 38 Yes | 13 No |
Post New Answer View All Answers
is ac supply can store
What is steady state response?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
HAI SENT HPCL APTITUDE QUESTION PAPER, MY EMAIL ID IS angus_eee04@rediffmail.com,angus_eee04@yahoo.com
i am trying to PSUs/govermeant jobs since last 2 years but still i m not success, plz help me.
Efficient electrical earthing in hard rock area
WE know that for Inductor X=2pifL,In DC f=0,then X=0 so,V=IX=0;But In the DC excitation of rotor of AC generator,DC motor field coil which coils are inductor so why does not applying DC voltage short the rotor coil of AC generator and field coil of motor?If it would then DC source might be damaged but it is not happened. Why does the strand conductor of Electrical power transmission line make twist?
how to find the capacitance value of the motor while running??
what is under coal gassification?
What happens to a motor if it is connected in Delta connection
Load break swicth maintenance procedure.
which fault is severe and why?between lll fault and lllg fault which fault is severe and y?
Define the term factor of inertia.
what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network
LET ME NOW MORE ABOUT icu and ics for circuit breaker. how we calculate the rating of circuit breaker and i c u and ics values