Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to select cable size?

Answer Posted / itsme

1. find load.... 8kw shower
2. find current Power/voltage ie. 8000/230 =34 amps
3. Use next fuse size up from current...40amp fuse/breaker
4. select a size cable suitable to carry 40amps
5. Find length of run. ie 20 meters.
6. carry out volt drop calculation

design current (34amps) x Length of run (20 meters) x
millivolt drop per meter (7.83 mvolts/meter for 4 square
cable) >>> 34 x 20 x 0.00783 = 5.44 volt drop!

if volt drop exceeds 9.2 volts use bigger cable

Is This Answer Correct ?    23 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to check the Bushings of the transformer?

1797


11 kg trivevter meter has rating of -/5amps. And pt ratio11000/110v and is connected with 11kv ct/pt unit of cr ratio 75/5amps. And pt ratio of 11000/110v while checking accuracy of meter with HT Accuchek meter what value of PT ratio and CT ratio to be filled in Accuchek meter

1914


If symmetrical fault occurs at the terminal of a synchronous motor then how the motor will act...explain it..

2117


How can I calculate the Mega watts required to run a plant having many electric motors and other electrical components.

2059


Is potential difference materials property ..? if yes tnen how.. explain brifly.

2032


i need mat lab program to find out the transmission line losses,regulation and losses

1887


what are the condition that makes hooter blow?

2426


Make a list observation on Transformer?

2416


How to calculate the multiplying factor for energy meter with ct ratio given

2002


In what condition the HT fuse breakes?

1999


How many methods use the load flow solution?

1319


1. What is differential relay? How it operates? 2.How to calculate the Short Circuit Impedance in Transformer? 3.What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works? 4. While testing the 33KV Busbar by using Hipot kit, what should be the test voltage we have to apply? 5. What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer? 6. Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example? 7. Why restricted earth fault protection is needed? Why can’t differential Protection is sufficient? 8. What should be the minimum and maximum ohmic value for earthing? 9. Why DC Currents are not used in transformer? 10. What is the Frequency while we step up the voltage from 220V to 11KV? Is it possible? Explain it?

2259


After completing iti in electrician, how can i get certificate of electrical supervisor? What ia requirements. For it?

1795


HOW TO CALCULATE S/C,O/C,E/F OF ACB.

2565


How to set a Zone 1 distance relay for distribution feeder?

1994