How to select a D.G set for calculated load of 110kW..?
Answer Posted / prakash veer singh
Our calculated load is 110KW . Normaly, we give 80% load on
DG for best and long opration . DG pf is 0.8.
So DG rating = 110/0.8
= 137.5 KVA
we use 150 KVA or high then.
| Is This Answer Correct ? | 92 Yes | 24 No |
Post New Answer View All Answers
Greeting to all members, How to calculate spill current when we have different ratio CT and Class for REF(Low Imp) I have 500/1A 5P20 @line side n 400/1A CL.X @ Neutral.
Why are the cores of large transformers built up of circular transactions ?
Difference between Lugs and Thimbles
what is a composite error in current transformers, why occurs & in which it will occur i.e, either metering ct/ protection ct
After taking shutdown of 11kv feeder, if you see 5kv by phasing stick in the cable side, is it possible to close earth switch in cable.
What do you mean by dependent and independent voltage sources?
How to decide cable tray size?
how rectifier transformer work in electroststic precipetatore(esp?
we have consol make 3 phase servo stabilizer for cnc m/c. while installing the earth neutral voltage is 1.7 volts at stbilizer off condition and when stabilizer get on en voltage reaches 4.8 volts (new earthing is done and neutral is helthy condition all phase to neutral volts 440,442,441 v)why this happen.solution for cause.
What is dc current source?
in dc series motor if field wdg is shorted then
if i get a drop in my 1st year and the i clear my 2nd year and 3rd year all clear and i dont have any back logs so can i be able to sit in campus selection??
Write the force balance equation of ideal spring element.
My load is 1635 KW. & current pf is 0.884, I have to improve it for 0.99.Please suggest what KVAR value is needed?
diff.between servo motor and ac motor