How to select a D.G set for calculated load of 110kW..?
Answer Posted / prakash veer singh
Our calculated load is 110KW . Normaly, we give 80% load on
DG for best and long opration . DG pf is 0.8.
So DG rating = 110/0.8
= 137.5 KVA
we use 150 KVA or high then.
| Is This Answer Correct ? | 92 Yes | 24 No |