Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to select a D.G set for calculated load of 110kW..?

Answer Posted / prakash veer singh

Our calculated load is 110KW . Normaly, we give 80% load on
DG for best and long opration . DG pf is 0.8.
So DG rating = 110/0.8
= 137.5 KVA
we use 150 KVA or high then.

Is This Answer Correct ?    92 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is capacitor voltage transformer?? how it is different from potential transformer?

2240


what is automatic voltage regulator?we can control the vlotage by using fuzzy controller in matlab?why we go for fuzzy?

2009


What is difference between Harmonic and Non harmonic Capacitor Bank?

2978


how to calculate maximum current

2384


specify the inbuilt protections in DG

2118


An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%

2018


Do u know any one? how to find out in motor rated amps? formula?

2075


what is the transiant condition in alternator? and how it can be prevanted?

2179


WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?

2281


DC transmission

2136


What is a Phase shift meter? Where can I get one?

2296


How can you calculate the size of the down conductor cable for the lightning protection system. Is 70mm2 cable can replace 95mm 2 bare copper cable when the copper tape size is 25Wx3 thk mm.

5451


why dc is used in control circuit for mv & hv switchgear instead of ac

1974


what is the effect of change in supply frequency on load angle of synchronous motor,all other parameters remaining same?

2414


Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?

4341