How to select a D.G set for calculated load of 110kW..?
Answer Posted / prakash veer singh
Our calculated load is 110KW . Normaly, we give 80% load on
DG for best and long opration . DG pf is 0.8.
So DG rating = 110/0.8
= 137.5 KVA
we use 150 KVA or high then.
Is This Answer Correct ? | 92 Yes | 24 No |
Post New Answer View All Answers
Thumb rule of cable size(rm>30 rm)X multiplying factor=ampere
pre arcing time of ehv breaker
What are the different types of transformers?
relation between power station capacity and voltage level?
which pump used in WTP explain the function of VFD how to dtermine capacitorbank of capacity one plant
how we control automatic generator i'e with to supply (main supply and local generator) when the main supply was break to supply the local supply automatically to begin supplying power.I now this control circuit is the combination of contactor time delay contactor switch and overload relay .but my question is how we combine those component thank you