I am an electrical power engineer and arranged power system
for a data center, I installed MCB, ELCB and erthing system
TN-C-S.
But some times several ELCBs Disconnect circuits at the
same time! what may be the reason? (the ELCBs are 25A ,30mA)
Answer Posted / chandra
Mr. Mehdi, Do check the neutral of all circuits wether they
are connected to same ELCB group. If one neutral from one
group is connected to other group this problem will occur.
Even though all neutral is common at final point, each
neutral will have to pass through the ELCB in order to
monitor the return cuurent.
| Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
. How to calculate the Short Circuit Impedance in Transformer? How to calculate the Short Circuit Impedance in Transformer?
how we can calculate 2 phase welding transformer rating or total power?
What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.
If the Brush of DC motor is shifted by 90 deg, then what happens to voltage and torque? Both voltage and torque are zero. how to justify the answer?
What are the limitations of Kirchoff's laws?
For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?
How to decide CT & PT ratings for a given transmission line carrying some rated voltage?
What is bridge rectifier and explain with details
How can we connect additional batteries to three phase ups? What are parameters we have to check when connecting?
Give details on how you intend to handle a challenging position you are posted to manage unexpectedly as a company staff?
What are high pass filter and low pass filter? and What are the flowmeter ?
Write down the name of 2 lady Bir Pratin of Bangladesh
Define what is power quality meter ?
How many types of instrument cables are there?
harmonics filter