I am an electrical power engineer and arranged power system
for a data center, I installed MCB, ELCB and erthing system
TN-C-S.
But some times several ELCBs Disconnect circuits at the
same time! what may be the reason? (the ELCBs are 25A ,30mA)
Answer Posted / chandra
Mr. Mehdi, Do check the neutral of all circuits wether they
are connected to same ELCB group. If one neutral from one
group is connected to other group this problem will occur.
Even though all neutral is common at final point, each
neutral will have to pass through the ELCB in order to
monitor the return cuurent.
Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
and gate circuit diagram,amplifier circuit diagram
which is better to use svc or synchronous condenser why ?
Can an inverter be used as a converter? How?
What is the estimated total hydropower potential of india?
what is p.s impedance measurement test in earthing transformer?
how to calculation increase power factor for single phase
Suppose a 3 phase, 2 pole, 440V induction motor is driving a flywheel of 600mm diameter, 150kg mass. By using v-belt and pulley, the speed is increased to 4500 RPM. What will be the effect on motor current?
What is the most accurate way of testing ELCB?ELCB is better than RCD?
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
What are the applications of the electric motors?
what is v/f control in VFD?
State the factors, for the choice of electrical system for an aero turbine.
how to check avr of dg set of 125kva
What is the function of the generator exciter?
When we have earthing mesh or underground earthing network in industrial plants, weather we have NT-S or NT-C-S kind of earthing system, so eventually weather we must use 4 or 5 wire in 400 volt level (For example 3×150+70 mm2 or 5×150 mm2) in this connection I would like to know exactly the paragraph of IEC or IEEE number