6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?

Answer Posted / mnm

Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

is the value of inductance depends upon the evalue of thitha in doubly excited machine?

1454


I have a current transformer with 1 main reading meter with transformer outside the building and a control panel having 5 CT reading meters with black round coils inside the building. I want to know, A) when current pass through the Transformers, will the current be reduced or be the same and after that B) when current pass through the CT meters with black round coils, will the current be reduced or be the same. C) in the above process will the reading of the main meter be same or different, from the total reading of all the 5 CT meters.

1371


What does the letter CTNM in negative phase sequence relay means?

1216


Circuit diagram of tube light without starter using electrical choke

3641


Starting times for soft starter & power factor is thier any standard or datas available in manufactures list. Kindly suggest.

1462






why voltage form factor of PT are increase , when it is ecpected heigher spikes in system. how it is calculated.

1645


what id a dry type transformers and its function ?

1343


Why line VTG = √3 phase VTG in star? How?

1172


what is the difference between surge protection capacitor and surge arrestor

1811


what parameters should we check to reduce the power bill

1830


what is the main parts of transformer? how it is functioning? pls giv the ans briefly.

1449


# 4 hi friends i m from electrical branch and seeking for tech. + apti. both papers of hpcl plz get it available as soon as possible my email id is sumit_lig189@yahoo.co.in

1564


I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400

1407


What do you mean by Frame 5 Gas Turbine as well as Mark II.

2044


what is the circutor?why we use it ?

1827