6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / mnm
Your selection is OK. Any breaker will have 110% voltage
withstand capability. Only thing is interruption capability
reduces, which is not relevent on no-load. On load, the
voltage of the transformer will reduce by nearly 6%, due to
impedance, making it just suitable.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
How you calculating the 30 Hp 3 phase AC motor of power what size of cable is used for this motor?
How efficiency of thermal plant can be improved?
Is a d.c.compound motor is use as a booster? how?
How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer
Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?
What is a differential amplifier?
why electron produce magnetic field when it is in motion?
Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.
why Lightning arrestor are made by 2 seperate stack of inslutor but why cvt are in single stack of insulator.
What is a fuse? How does it work? What are materials used?
why in the three pin plug all 3 pins are cutted ?
Working of microwave oven?
Details about Flux Compensated magnetic Amplifer starter for motors
when we gave dc supply to 220v dc motor its rpm is 1200. then we gave 180v. how many rpm of its motor. gave answer with calculation at my ID.... ravizak@ymail.com
In India the supply voltage is 230 volt A.C. During the negative half cycle phase becomes neutral and neutral become phase? or what will happen during negative half cycle? how the electrons flow during positive and negative half cycle?