why we avoid parallel operation of diesl generator?
Answer Posted / johnson m.c.
1) Potential of both alternators must be equal. Both must
have same output voltage.
2) Phase sequences of both the alternators must be same.
The RYB phases of one alternator must
be connected the RYB phases of the other alternator.
3) Frequency of both the alternators must be equal. If one
alternator is operating at a frequency of 49
Hz and the other one is delivering voltage at 51 Hz, then
load on the second alternator would be
more. We have to increase the speed of the prime mover of
the first alternator in order to effect a
match in frequencies.
4) Phase angle of voltages of the two alternators must not
be more than 10 degrees.
5) During manual operation of synchronization, the load
could witness kick (which is a peak of
current). This kick could burn the alternators on the load.
The only solution is the use of automatic
synchronisation equipment. However, expert engineers could
close the CB of the second
alternator when the difference of phase angle between the
two voltages is 2 degrees.
6) The alternators must share loads with respect to their
ratings.
7) The alternators must have similar voltage drooping
characteristics.
8) The engines of the alternators must have similar
governor characteristics;
| Is This Answer Correct ? | 10 Yes | 4 No |
Post New Answer View All Answers
how to read idmt curva
how to carry out Magnetizing Current Test on Distribution transformer and what purpose we are doing this test. why transformer rating in always in KVA ? what ispositive, negative, zero sequence impedence? How ElCB tripping if Neutral touch with ground Why AC & DC capacitor are use in UPS ? why motor rating in KW? how to syncronize two dg sets
why EMF IS INDUCED IN A CONDUCTOR WHEN FLUX LINKING WITH IT CHANGES ACCORDING TO FARADAYS LAW.
How much dc volt applied in cathodic protection system?
what are the different kind of cables used for transmissions?
what are the different methods for the starting of a synchronous motor.
WHAT IS SITTING AMPS IN OVER-LOAD RELAY FOR 1PH OR 3PH MOTORS?IF ITS NAME PLATE GIVEN MAX AMPS 10AMPS?
features of hbc fuses
am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?
if 3400kw slipring motor rotor shorting done and motor started on mv drive ,what will be the rotor shoring current
What is the difference between the transmission line and distribution line?
What is meant by bus bar protection?
What is resistance reading of earth copper rod with grid and without grid?
circuit diagram of trip circuit supervision relay
What is meant by earthhing of a magnetic flow meter and when to use empty pipe detection?