when neutral will carry the current?what could be the
magnitude?
Answer Posted / ajay patel
In case of SIngle Phase System Neutral will carry current
of same magnituge as phase current.
In case of 3 Phase, Star Connected System, neutral will
carry current only during unbalanced or Phase to Neutral
fault condition. During balanced condition current through
neutral is zero(Ia+Ib+Ic=0). In case of Unbalance load
Neutral Current can be maximum as phase current. & In case
of Phase to Neutral Fault Magnitude of neutral current will
be same as fault current. In case of Phase to Earth Fault,
neutral current will be 0. Earth current is suppose to pass
through Earthing grid or Armoure of cable.
| Is This Answer Correct ? | 14 Yes | 4 No |
Post New Answer View All Answers
i m in need of current rating chart of heavy duty pvc/xlpe, cu/al cables. can somebody provide me? if yes, plz send me at ashish_patel111@yahoo.com
what is the power rating of CPU, CRT type moniter, LCD type moniter,scanner Approx.
Why derating factor os applied on Cables?
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
should %impedance be high or low in a power transformer? if so why?
In a flange coupling, the flange bolts are designed for
Differentiate between Zero and Negative sequence current
In EB metering we face problem kva jump even in no load condition.can any one help to control this
How much inductance or resistance require as a starter in series with induction motor of specific capacity(e.g. 5 hp) ? What is formula for it ?
for 750 kw LT load what will be the ht kva
how to calculate earth fault relay current and CBCT ratio
what is doid
what is earthing transformer? draw the winding dia.of earthing transformer.
HOW TO TEST A LIGHTENING ARREST ER ?
Why are cables rated for 40 KA for 0.25 Sec fault current rating?