i have 28/32 MVA power transformer with 11/6.6 KC voltage
rating and 12%impedance.it have star connection at both
side.but it have another thied winding tertiary
winding.what is used of this winding.
pl tell me
Answer Posted / ajay patel
How your tertiary Winding is connected? what is the rating?
If all three phase terminals are bruoght out then it can be
used as additional seondary winding. But If this tertiary
is connected in Open Delta & 2 termianls of open delta
brought our for Earthing. That means this is installed for
Harmonic purpose. If you have rectifier, Big VFDs or such
load which can generate Theird Harmonic in big amount then
these third harmonic can be reflected in entire Grid, if
your transformer is Star - Star. Which is may damage other
equipments / consumers also who are connected with same
supply. Hence it is necessory to control 3rd harmonics in
grid. For this you can provide Delta Primary for
Transformer. But you dont have delta in primay tehn you
have to provide Tertiary winding with open Delta. This Open
delta is closed out side of Transformer & Complete Delta is
formed. This Delta winding should be earthed to minimise
harmonic disturbance in the system. Please check, do you
have earthed tertiary? Is it in Delta?
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how do we calculate length of starting time and repeated starting of a direct online starter?
Which device of PlC does share load between DG sets when DG are running in perallel?
we have amp, voltage, kw, length detail then how to calculte copper & alluminium size of conductor of 3-phase induction motor
What are the three constants associated with a steady state error?
what is relay what is protection & contact multiplying relays where it is used function in brief
Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com
what about the power of wattmeter at starting and loding?
What is difference between YNyn0 and YNyn ??
If I want to buy a new Xformer for my plant what are the main parameter will I need to check?
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The rotor reactance at stand still is A 2 ohm B 1.25 ohm C 3.15 ohm D 2.25 ohm
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?
What are the different sign conventions used in electric circuits?
can we use engine degreaser for electrical motors?
ROC converges if pole and zero lies inside a) origin b) z=1 c) pole d) zero ? Explanation please? if ROC does not converges then?
On a 3 winding transformer YNynd11, how do you apply REF protection to the Delta tertiary winding that is supplying auxiliaries to a substation?