What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / rajukumar sripelli
HI ,
this is rajukumar sripelli from REPUTED TRANSFORMER
MANUFACTURING COMPANY ..testing department ..
AS u all above is not fully correct....
Magnetic balance test is done on TRANSFORMER to see whether
the transformer core is magnetically balanced or
not...AND ALSO WINDING CONDITION....IN FAULT CONDITION DUE
TO HIGH CURRENTS WINDING MAY BE DAMAGE....
for example
we r having delta HV and star winding LV side ...
HV SIDE WE WIL BE HAVING THREE BUSHINGS....THOSE R 1U,1V,1W..
HV SIDE WE WIL BE HAVING FOUR BUSHINGS.....2U,2V,2W,2N...
WE CAN DO THIS MBT (MAGNETIC BALANCE TEST)WITH 1PHASE
SUPPLY(1PHASE AND NEUTRAL(230V)) OR WITH 2-PHASE
SUPPLY(2-PHASES(440V))
1ST STEP OF MBT: GIVE POWER SUPPLY 1-PHASE OR 2 PHASE
BETWEEN 1U AND 1V ,MEASURE THE VOLTAGES BETWEEN 1V-1W AND
1U-1W AND ALSO 2U-2N,2V-2N,2W-2N..
SO HERE IF THE CORE IS CORRECTLY BALANCED THEN WE WILL GET
RESULTS AS FOLLOWS
1U-1V 1V-1W 1U-1W 2U-2N 2V-2N 2W-2N
440 300 140 90 50 40
THAT MEANS HV SIDE : 1U-1V = 1V-1W + 1U-1W
I.E 440V = 300 + 140
AND ALSO LV SIDE : 2U-2N = 2V-2N + 2W-2N
90 = 50 + 40
STEP 2: AFTER DOING THIS ..INTERCHANGE THE CONNECTIONS
BETWEEN 1V-1W AND MEASURE THE VALUES AS ABOVE...
STEP 3: AFTER DOING THIS ..INTER CHANGE THE CONNECTIONS
BETWEEN 1U-1W AND MEASURE THE VALUES AS ABOVE...
IF ANY FAULT IS THERE IN TRANSFORMER WE CAN NOT FIND GOOD
RESULTS....
IF THE WINDING IS DAMAGED .... WE WILL GET ZERO VALUES ....
ex: HV SIDE 1U-1V = 1V-1W + 1U-1W
440V = 440 + 0
AND ALSO LV SIDE : 2U-2N = 2V-2N + 2W-2N
90 = 90 + 0
THIS IS THE ACTUAL APPLICATION OF MANGNETICA BALANCE TEST...
THANKS....
| Is This Answer Correct ? | 287 Yes | 9 No |
Post New Answer View All Answers
What do you mean by the zone of protection?
what is quality factor in series resonance circuit and calculate the factor of voltage magnification? how it happens?
What are the internal and external faults?
What is resistance of 50meters, 16sq.mm, single core copper cable?
what is calculation mathod/formaulla for deciding Size of busbar (Copper/ aluminum)for L.T. panel on Various Fault level like 50kA,25kA,10kA
Do u know any one? how to find out in motor rated amps? formula?
hi....I am from india..i have completed my engineering in electrical and electronics field with 58.4% and my IELTS score is 5.5 bands....Recently i received my I-20 in computer and information science from Troy university in Alabama.On 18th i have a visa interview can u please tell me what type of questions i have to answer ??????
why we can stote dc? why we cant store ac?
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
PLEASE SEND ME NTPC RELATED INFORMATION LIKE WHICH TOPICS HAV MORE SCOPE,BOOKS TO READ,CUT OFF...PLEASE.mail at thiru.1203@gmail.com
how to calculate distance between busbar supporters for LT panel, what are the factors influencing in this design
how to calculte capacitor range for single phase induction motors??pls tel
We have 110Vac ,10A ac supply which is converted into 110VDC & How much DC current? which factor is reqired for dc current calulation?
I want to make street light with solar system ... What may I do for procedure and how much of estimation for each material ... If any one knows guide me and inform this id : aravindd7@gmail.com
why current is constant on d.c?