How to select a D.G set for calculated load of 110kW..?

Answer Posted / v.c.k

For the Calculated load of 110KW

for DG Selection,we mush know phase

therefore we consider 3 phase

A=kw*1000/1.732*45
=110*1000/1.732*415
=110000/718
=153A

therefore we select the next higher stage DG, its means
225KVA (If available we choose 175KVA or 200KVA)

Is This Answer Correct ?    14 Yes 29 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how we control automatic generator i'e with to supply (main supply and local generator) when the main supply was break to supply the local supply automatically to begin supplying power.I now this control circuit is the combination of contactor time delay contactor switch and overload relay .but my question is how we combine those component thank you

1512


What types domain of laplace transforms? What behavior can laplace transform predict how the system work?

668


why dc is used in control circuits for MV & LV switchgeras instead of ac

1471


Difference between RCCB, RCBO and ELMCB.

3569


How to calculate the input cable rating for 10kva ups (3phase input and single phase output and also 3phase output, battery rating 65Ah)provide the formula also.thnx

1775






Why Transformer Neutral having one earth pit ( more earth electrode resistance) whereas body have many earth pit ( less earth electrode resistance)?

3843


1.how many earth pits are required for 1000 k.w plant include substion , transformer ? 2. how many earth pits are required for 500kva generator.what is formula to calcute?

2291


HOW TO CALCULATE THE REGULATION OF 100 AND 25 KVA TRANSFORMER

1449


where is core-type and shell-type construction suitable for transformers ?

1647


model question paper for supervisor trainee

1601


what is the effect of change in supply frequency on load angle of synchronous motor,all other parameters remaining same?

1897


how we calculate the dick for a pole?

1717


Why are short circuit ratings always 16kA,25kA,36kA and 50kA.Who has fixed these?

3812


Generator,motor and alternator Working principal Please explain easily

998


can some one clearly explain why -48 volt DC use in telecom site????

1224