WHAT HAPPEN IF GENERATOR TURBINE IF TRIP?

Answer Posted / santosh chinchalkar

If T.G set is running on synchronus speed and turbine is
triped on low steam pressure or some other resion, The
Generator will take the power from system instated of
giving and Generator will work as Motor,that will harmful
to Turbine blades.for avoiding this reverse power
protection are used to stop the Generator.

Is This Answer Correct ?    49 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what are the ''pitting rings''and how cn they be controlled in a series generator

1363


RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?

1527


A motor running with lenze frequiency inverter stops if I REDUCE SPEED with 25% load.If I run it in High speed and medium speed running smoothly with full load.please help me to solve it.

1520


why we change the direction of winding in rotor ?how we make the north and south pole?

1578


what are the usual topology of transformers at different substations in the power system and why that particular topology is choosen. what are the limitaions of that topology?

1603






How can we increase the capacity of Energy.?

1671


How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?

1629


DERIVE AN EXPREION FOR MAXIMUM POER TRANSMISSION, WHAT ARE ITS APPLICATIONS.

1584


calculate external resistance values to add to the rotor of a slip ring induction motor. STATOR- 415 V, 3 phase delta, 1100 A, 50 Hz, 1490 rpm, pf 0,86 ROTOR - 660 V, 590 A, 50 Hz. STATOR current at each steps STEP1-600A,STEP2- 800A,STEP3-1000A,STEP4-1100A.

3065


What do you understand by oldham's coupling ?

644


1. The DC generaror,s induced output emf is connected with a DC motor(as load). when increasing the load of the motor by using brake drum or any way. what are the parameters will changes in both motor and generator(voltage, current, resistance, frequency, speed, torque, power, flux etc...) 2. Similarly for AC generator and AC motor 3. similarly if using DC batteries instead of DC generator, What happens?

1688


advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor

1385


in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?

1835


how we arrange the hv side with delta connection in case 33/11kv of transformer.

1536


I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400

1409