How to select Main CB Rating for 187 KW Load?

Answer Posted / bala

Selecting main cb rating depends on the type of load if it
is combination of small loads (upto 10kw) 400amps mccb is
enough.
1. if it is one motor load. first we have consider what
type of starter we are going to use. in case of star delta
starter select 600amps mccb. in case of VFD and softstarter
400amps mccb is enough.

Is This Answer Correct ?    4 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the function of attenuator in cro?

743


Could Please Explain briefly. Why used stabilizing resistance series with High impedance bus differential protection relay.

1282


To prove the capacity of a 10MVA transforemr with 6.5% impedance by a short circuit test how much power is needed to inject an impedance voltage if we have to arrive for its rated current?

1450


How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?

2578


why we use copper earthing for neutral while for body GI.

5059






how to select proper cable for ct wiring so that drop within the limit.

1466


how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.

1748


What are the two types of compensation?

632


what is the clear formula to calculate cable size for a load

1484


Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?

1582


How grounding is different than earthings?

724


Define availability (operational)?

663


What are the advantages of hydropower?

663


Please brief what is sinewave

1735


How earthing of switchgear system to be done.

1460