how we can calculate which capacity capacitor bank we have
to add for improve pf?
Answer Posted / z_hosen
More simply,
Let total power is 1500kw
assume
cos 1 =power factor before improvement =0.75
cos 2= poer factor after improvement =0.98
tan1=0.88
tan2=0.2
and
kvar 1= power*tan1=1500*0.88=1320kvar
kvar 2=power*tan2=1500*0.2=300kvar
now, required rating of capacitor bank =kvar1-kvar2
=1320-300
=1020kvar =1000kvar
thanking u
z_hosen@yahoo.com
Is This Answer Correct ? | 11 Yes | 4 No |
Post New Answer View All Answers
how to interlock 3 nos MCCBs using under voltage coil. please provide me circuit diagram?
what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).
Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV
how commomn gate triggering is given for TRIAC ? other thyristor wont be efffected?
Why can't we take NO LOAD TRIAL of motors having V1 mounting??
all details of DG UPS HVAC
what is the pre charge circuit,what will be work which function it will be use plz tell me
what is the interrelation between voltage current torgue speed and magnetic flux in case of different types of electric motors
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
how to get electrical supervisour certificate in gujarat
how to calculate micom relay earth falt time and current sertting
block diagram of 2 ups system connected in hot stand by mode?
dear sir/madam i want to get some knowledge about RRB EXAMINATION(section engineer) 1- what is minimum cut off 2- wht portion is major portion . 3- can any body provide Sample paper. thanks & regards ashish
what does a k rating in a transformer means?
how to calculate percentage impedence at 75 deg C at normal tap