how can we know cable size for a given current?
if any one have catalogue plz mail to
vijay_raju369@yahoo.co.in
Answer Posted / vasu
Two things are very much common on the power system engineering field while doing a cable sizing, these are:
1)LT
2)HT
Cables are separately sized based on voltage levels as said above.
Formulas used for LT side:
Full load current = KW/(KV x sqrt3 x PF x η)
Voltage Drop =
sqrt 3*IFL*(R COS Ø + X SIN Ø)*L/(KV*10000*N.R.)
where
IFL = Full load current of the Load connected in Amps
KW = Rating of the Load connected
KV = System Voltage
R = Resistance of the cable in Ohm/Ph/KM
X = Reactance of the cable in Ohm/Ph/KM
L = Length of the cable in meters
N.R = No of Runs of the cable
cosØ = Power factor of the system
PF = Power factor
η =efficiency
Voltage Drop =
sqrt 3*Ist*(R COS Ø + X SIN Ø)*L/(KV*10000*N.R.)
where Ist=starting current which can be 6 times the FLA of current.In technical term it is called as LRC(locked rotor current)
HT side:
Full load current = KVA / KV x sqrt 3
Short circuit current :
A = Ish x sqrt(t)/ k
Where
t = short circuit time in sec
k = constant
A = Conductor size in Sqmm
Ish = Short circuit current in Amps
Derating Factor :
Ambient temperature correction factor for cables laid in 0.9 Trays at 50 degree C = 0.9
Group derating factor:
Multi Core cables
Cables are laid with a spacing of one Diameter and routed in cable trays and trays in tiers by 300mm =0.9
Ageing factor= 0.95
Therefore the Total derating factor = 0.9 x 0.9 x 0.95 = 0.7695
Total Derating Factor= 0.77
The rest calculation for voltage drop are same as that of LT side
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
what is the necessary of using inductance property in transmission lines even through resistance is used to opposes the high current flows in that?????
what is meant by IGBT how they differ from tyristor ?
how is positive, negative, zero sequence is happen.. how is effect on 3 phase system
Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.
how to electrically make connection to ferroli GN2N?
how will we calculate the copper wire load..
Differentiate between magnetic field and magnetic flux?
Why is voltage is required to be within permissible range for an electrical equipment?
what are the preventive maintanance actions taken for air circuit breaker? please answer me
how can maintaince the acb contactor moveing and fixing kit
What is mean by STUB protection?
In EB metering we face problem kva jump even in no load condition.can any one help to control this
Define active filter?
how r charge carriers produced
Define super node?