how can we know cable size for a given current?
if any one have catalogue plz mail to
vijay_raju369@yahoo.co.in
Answer Posted / vasu
Two things are very much common on the power system engineering field while doing a cable sizing, these are:
1)LT
2)HT
Cables are separately sized based on voltage levels as said above.
Formulas used for LT side:
Full load current = KW/(KV x sqrt3 x PF x η)
Voltage Drop =
sqrt 3*IFL*(R COS Ø + X SIN Ø)*L/(KV*10000*N.R.)
where
IFL = Full load current of the Load connected in Amps
KW = Rating of the Load connected
KV = System Voltage
R = Resistance of the cable in Ohm/Ph/KM
X = Reactance of the cable in Ohm/Ph/KM
L = Length of the cable in meters
N.R = No of Runs of the cable
cosØ = Power factor of the system
PF = Power factor
η =efficiency
Voltage Drop =
sqrt 3*Ist*(R COS Ø + X SIN Ø)*L/(KV*10000*N.R.)
where Ist=starting current which can be 6 times the FLA of current.In technical term it is called as LRC(locked rotor current)
HT side:
Full load current = KVA / KV x sqrt 3
Short circuit current :
A = Ish x sqrt(t)/ k
Where
t = short circuit time in sec
k = constant
A = Conductor size in Sqmm
Ish = Short circuit current in Amps
Derating Factor :
Ambient temperature correction factor for cables laid in 0.9 Trays at 50 degree C = 0.9
Group derating factor:
Multi Core cables
Cables are laid with a spacing of one Diameter and routed in cable trays and trays in tiers by 300mm =0.9
Ageing factor= 0.95
Therefore the Total derating factor = 0.9 x 0.9 x 0.95 = 0.7695
Total Derating Factor= 0.77
The rest calculation for voltage drop are same as that of LT side
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
In 90 kva alternator that produce the output voltage is 115(p-n),200(p-p) at 1500 rpms means what ampere it produced ?
How to connect the chemical earthing and complete process tell me plz
What do you mean by per capita requirement of electrical energy in india
What is minimum permicible value of leackage current for LT Panle when applying voltage up to 3 KV for 5 Minuits?
what is the difference between surge protection capacitor and surge arrestor
Dear Mr B C pal...Can you plz. put some light on principle of operation of Z-Ct in conjunction to its use with 1Cx1000Sqmm HT Cables & Directional Ground Fault / Over Voltage Relays...Regd..Parag v K 9899115632
What is 11 N1 and 12 N2 in single phase Transformer ?
what is Anti-pumping?
how can i get an electrical c-certificate?
what is efficient motors and how it is different from normal induction motors
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
how many types control panel of a 132/33 kv substation
what is mean by parallel operation of permanent magnet generators
list the advantages of RCCB over other circuit breakers?
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega