Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What it indicates by 25/41MVA on transformer?

Answer Posted / t eswara rao

25 / 41 MVA rating means that
25MVA rating with normal cooling arrangement.
41MVA rating with special cooling arrangement, like External
cooling fan arrangement for more cooling

For ex: 25MVA with ONAN (Oil Natural & Air Natural)
41MVA with ONAF (Oil Natural & Air Forced)

Is This Answer Correct ?    21 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What will happened if the neutral of the (star connected secondry) Xformer disconnected? (if its Above KVA rated one)

2146


types of central Air conditioner plant?

2140


What is the main purpose of c.f.b.c.boiler

1688


How servo stabilizer works.

2102


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

1901


xfhnchncv?

1884


How the frame size of a flange mounted AC induction motor is calculated?

2044


For an induction motor wat is the loading/unloading cycle duration or interms of L/UL ratio/ percentage?

2082


what is the difference between single ratio, multiple core and multiple ratio, multiple core ? please explain.

2175


What are different types of control systems?

1236


Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.

2159


how to calculate cooling requirement of datacentre from electrical load?

2387


RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?

2063


what is residuel magnetism. and how order lead acid batteries for 24 volt. emergency lighting system.

1968


Explain about technical and non technical losses in distribution system?

1043