What are the difference between C-Curve and D-Curve for
MCB's.
Answer Posted / bright spark
There is no A type.
B C and D types all consist of 2 similar parts:
The thermal trip, this is the same for all MCBs of the same
rating eg 6A.
The Magnetic trip, this is where the difference is.
B C and Ds have an increasing degree of initial "tolerance"
to overload.
B types have a limit of 3 - 5 times the rating.
e.g. a 6A MCB would trip with a surge of 18-30A.
C types have a limit of 5 - 10 times the rating.
e.g. a 6A MCB would trip with a surge of 30 - 60A.
D types have a limit of 10 - 20 times the rating.
e.g. a 6A MCB would trip with a surge of 60 - 120A.
Now you would think that the B curve would be the safest,
and it is, but not very tolerant of power surges. If you
have quite a few lights on in the house and switch on
another, this can be enough for that initial start up surge
to trip you whole lighting ring, and a reset at you consumer
unit. B types are notorious for this, but ideal for a ring
final where you don't have too many outlets, gives ideal
protection.
As you can see a type D 6A MCB can tolerate a 120A surge, so
a 32A Type D would tolerate an initial surge of 320 - 640A
before tripping!. Domestic Consumer Units will have a master
trip of @60 - 100A (80A is most common), hence why there is
never a need for type D in the domestic environment, not
unless you have a 3 phase incomer and have a car production
line in your back garden instead of a washing line!.
| Is This Answer Correct ? | 205 Yes | 17 No |
Post New Answer View All Answers
specific difference of ICT&Auto Transformer
Explain marx circuit.
how we can do the insulation on secondary of ct explain and so that tan delta will within limit
how to test YNyn0 vector group in transformer?
Diagram on interconnectivity of 11kv transformer with RMU (i.e, one incoming and two outgoing or two incoming and one outgoing)
Why the power factor improvement is so important in industrial loads
How do we arrive at selecting reactive capacitance value as 30% of h.p rating of motor?
if the motor rated speed is 950rpm. how to change the above rated speed? is it possible?
11 kg trivevter meter has rating of -/5amps. And pt ratio11000/110v and is connected with 11kv ct/pt unit of cr ratio 75/5amps. And pt ratio of 11000/110v while checking accuracy of meter with HT Accuchek meter what value of PT ratio and CT ratio to be filled in Accuchek meter
what is EIB lighting control system? what is the advantages of this system?
Mention what are the types of semi-conductors?
what is breathing?
Define availability (operational)?
Define non-touching loop.
Please tell me the earthing procedures adopted for the STAR-STAR 3 Phase transformer in india and give a better sugession for earthing