HAI,HOW TO SET THERMAL OVERLOAD RELAY FOR DOL STATRTER
FEEDER AT START AND RUNNING?
Answer Posted / fairos
First, for thermal overload relay has no meaning in term of setting it while on running or starting. It purely based on rated current of the motor.
when you look at the nameplate of the motor there should be a data that mention "duty" which normally either 1, 1.1 or 1.2 in value. If the duty is 1 then you can only set the overload relay at 100% of the rated current. If duty is 1.1 then the motor is allowed to operated at 10% higher than it rated current hence you can set your relay at 110% of rated.
Generally people would set at 10-15% higher than rated current. But sometimes being conservative is okay, which you can set the relay below the rated current. This can be done as long as it is not tripping unnecessarily.
| Is This Answer Correct ? | 22 Yes | 3 No |
Post New Answer View All Answers
for 11KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV UG system what will be typical per KM "R" "L" "C" parameter.
what is the eight bit unit?
How to calculate the current of Highpressure Mercury Vapour Lamp?what is the basis?whether we have to consider power factor or not?
What is the bundle conductor?
We have 5 Distribution sections with variable loads&We have 3 Gensets(500kva,380kva&250kva) our total load is between 400kva to 600kva. so how could we connect 3gensets.
What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works?
Thermal withstand capability under full short circuit conditions, in terms of number of times of occurrence of short circuit and corresponding anticipated percentage reduction in transformer life.
How to calculate or formula to calculate rhe power in 2 phase system ??
i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....
what work will do diffrential realay DG set
i karmveer bharti persuing b.tech . plz send me syllabus and name of reference books. for preparation of section eng.
How to calculate the electrical load for a standard telecom BTS shelter and choose the DG set capacity for the same load?
what is a power factor?
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
Write the programming software name for LG, SIEMENS,Messung,AB