Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.

Answer Posted / pratheesh

We can calculate the total output current of a 300kva ups.

P=&#8730;3*V*I*Cos&#934;
Where P= Output power of UPS here 300000VA
V= Output voltage of UPS ( I hope this is a 3 phase
415 volts UPS)
I= Output current. (We need to calculate)
Cos&#934;= Powerfactor of the load. Varies depends the
nature of load(Inductive, Resistive or
Capacitive. We can assume this value is as 1
because we dont know the powerfactor, nature of
load.

So I= P/(&#8730;3*V*Cos&#934;)
= 300000/(1.73*415*1)=Approximately 420A per phase(if
the load distribution is balanced on each phase)


So, If the UPS runs on 40 to 45 percent load, it will take
around 170 to 190 Amps on each phase.

Is This Answer Correct ?    14 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is servo motor and how it works?

2280


What is the type of earth fault protection used in battery? explain.

2287


Do inductive loads have distorted current waveforms ?

1914


what is cause of static electricity? I experience shock when i touch metal equipment in a room ,furher check shows earth leakage showing 80ma at the DB near to the 400 MCCB?

1878


What is zero of the system?

1080


Why it is possible to use PWM with a STATCOM and not with a conventional TCR based SVC

2093


i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?

1384


What safety precaution are to be taken for avoiding electric hazards ?

1850


Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?

1413


Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output

1814


if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?

2535


I want to calculate how much capacitor we connect to maintain the unity power factor? Is there any formula? Pls give me the answer

1912


WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?

2144


what is the ms flat constant for calculating earth mat design calculation?

2493


tell me about roaster switch .& what is the function in transmission & distribution?

2644