What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.
Answer Posted / pratheesh
We can calculate the total output current of a 300kva ups.
P=√3*V*I*CosΦ
Where P= Output power of UPS here 300000VA
V= Output voltage of UPS ( I hope this is a 3 phase
415 volts UPS)
I= Output current. (We need to calculate)
CosΦ= Powerfactor of the load. Varies depends the
nature of load(Inductive, Resistive or
Capacitive. We can assume this value is as 1
because we dont know the powerfactor, nature of
load.
So I= P/(√3*V*CosΦ)
= 300000/(1.73*415*1)=Approximately 420A per phase(if
the load distribution is balanced on each phase)
So, If the UPS runs on 40 to 45 percent load, it will take
around 170 to 190 Amps on each phase.
| Is This Answer Correct ? | 14 Yes | 8 No |
Post New Answer View All Answers
what is servo motor and how it works?
What is the type of earth fault protection used in battery? explain.
Do inductive loads have distorted current waveforms ?
what is cause of static electricity? I experience shock when i touch metal equipment in a room ,furher check shows earth leakage showing 80ma at the DB near to the 400 MCCB?
What is zero of the system?
Why it is possible to use PWM with a STATCOM and not with a conventional TCR based SVC
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
What safety precaution are to be taken for avoiding electric hazards ?
Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?
I want to calculate how much capacitor we connect to maintain the unity power factor? Is there any formula? Pls give me the answer
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
what is the ms flat constant for calculating earth mat design calculation?
tell me about roaster switch .& what is the function in transmission & distribution?