Answer Posted / ilononurb
we can take the break down voltage of transformer oil by
using oil tester. Take oil sample of tr oil and put in to
the testing oil pot with the spere electrode of 2.5mm gap.
Applied gradually the voltage till the oil losses its
dielectric stenght. breakdown voltage will display to the
oiltester meter. As per IEC 156 Standards it should be
40kv.eff.
| Is This Answer Correct ? | 78 Yes | 8 No |
Post New Answer View All Answers
what is the defination of Cable database? What are the points are considered while preparing cable database? Is there any sample available for cable database?
What will be the effect if I use inverter as UPS mood?
what is the size of ht cable of 33kv ht line and transformers ratings are 1 Mva and 5mva.please send formula also.
how does an encoder work???
What happen when neutral point connected to core balance current transformer? (Neutral point of an alternator of a 180KVA DG. Neutral point connected to CBCT means enter to the CBCT)
a starter used for squirrel cage induction motor?
how to differentiate a mpcb,mcb with a contactor? Explain their working operation
What is The Resistance Formula
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
Explain marx circuit.
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
How each of the following losses occur in d.c machines (i) copper (2)core (3) windage (4)friction please help me
What are the main significances of root locus?
What fomula is used to calculate: 1. rated frequency withstand voltage, and 2. rated lightning impulse withstand voltage.