Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how we can calculate which capacity capacitor bank we have
to add for improve pf?

Answer Posted / abdulsubur

p total connect load in kw =932

cos 1 =power factor before improvement =0.8 assume
cos 2= poer factor after improvement =0.9
kvar 1= ptan1 932*0.75=699.03kvar
kvar 2=ptan2 932*.4843=451.39kvar
req rating of capacitor bank =kvar1-kvar2
=699.03-451.39
=247.64kvar =250kvar

Is This Answer Correct ?    12 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the soft starter principle? how is connection diagram? what is the procedure for checking the connection?

2220


Which cable is use for rtcc control panel

1811


how does WTI work ?

2069


Why earthing is necessary for any equipment?

1787


What is rotary phase converter?

1133


Hi Everyone ! My Name is Hakim ullah khan please i need formula of Cable Rating because i want to calculate by self without check any Table Chart... Thank you.....

1778


What is different between Difnit time and instatous over current relay

2626


what is negative d.c. voltage, why this voltage is used in base transciever station.

2203


Plz tell me how we can find that particular company has vacancy or not

2331


Can you explain about pole discrepancy scheme

2234


In Air circuit breaker LSIG protection unit is used. Without fault in cables (2 runs 3Cx150Sq.mm Copper, 1Kv grade, XPLE armored cable IR value is more than 550Mohm @ 500V Megger) and load section Long time Overcurrent protection is triggers and trips the unit. We changed LSIG protection with new factory tested unit. Even then fault is persisting. Please suggest the possible causes

861


can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?

2362


How capacitor improves pf

1770


What consists of 2 or more thermocouples to be connented series?

2377


Which material is used for the core of a transformer and why?

1162