how we can calculate which capacity capacitor bank we have
to add for improve pf?
Answer Posted / abdulsubur
p total connect load in kw =932
cos 1 =power factor before improvement =0.8 assume
cos 2= poer factor after improvement =0.9
kvar 1= ptan1 932*0.75=699.03kvar
kvar 2=ptan2 932*.4843=451.39kvar
req rating of capacitor bank =kvar1-kvar2
=699.03-451.39
=247.64kvar =250kvar
| Is This Answer Correct ? | 12 Yes | 4 No |
Post New Answer View All Answers
what is the soft starter principle? how is connection diagram? what is the procedure for checking the connection?
Which cable is use for rtcc control panel
how does WTI work ?
Why earthing is necessary for any equipment?
What is rotary phase converter?
Hi Everyone ! My Name is Hakim ullah khan please i need formula of Cable Rating because i want to calculate by self without check any Table Chart... Thank you.....
What is different between Difnit time and instatous over current relay
what is negative d.c. voltage, why this voltage is used in base transciever station.
Plz tell me how we can find that particular company has vacancy or not
Can you explain about pole discrepancy scheme
In Air circuit breaker LSIG protection unit is used. Without fault in cables (2 runs 3Cx150Sq.mm Copper, 1Kv grade, XPLE armored cable IR value is more than 550Mohm @ 500V Megger) and load section Long time Overcurrent protection is triggers and trips the unit. We changed LSIG protection with new factory tested unit. Even then fault is persisting. Please suggest the possible causes
can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?
How capacitor improves pf
What consists of 2 or more thermocouples to be connented series?
Which material is used for the core of a transformer and why?