hi this is noor in my work spot, i arranged THERMOCOUPLE in
the place of RTD. (in FEED WATER tank). can i use T/C or not?
Answer Posted / manash ranjan jena
You can use a Thermocouple in place of RTD but you need to
change your control loop instruments accordingly. As T/C
output will be mV where as RTD output is always change in
resistance. Please check the input of your measureing
instrument, if that is a universal input circuit then you
can use a T/C inplace of RTD.
Is This Answer Correct ? | 20 Yes | 2 No |
Post New Answer View All Answers
dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.
In most instances, Inertia processes are quite uncommon. Give an example of a combined Resistance and Capacitance situation.Describe an application, which according to your understanding of the subject matter, comprises of both Resistance and Capacitance effects.
how many type conductivity sensor ?
How to calculate P,I&D value in PID controller ?
What is the use of temperature compensation?
What is shielding effect?
what is intrinscily safe system and where we use?
in differential pressure transmitter,min&max pressure range for hp&lp
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
this site is owned by an nonsense
What is hp & mp seperator .& what is its working principle ?
why we use impulse line of flow transmitter at 45 deg. angle both side of orifice plate.
please send the drdo exam paper
any questions on motor and energy conversions machines?
How to calibration coriolis flow meter?