hi this is noor in my work spot, i arranged THERMOCOUPLE in
the place of RTD. (in FEED WATER tank). can i use T/C or not?
Answer Posted / manash ranjan jena
You can use a Thermocouple in place of RTD but you need to
change your control loop instruments accordingly. As T/C
output will be mV where as RTD output is always change in
resistance. Please check the input of your measureing
instrument, if that is a universal input circuit then you
can use a T/C inplace of RTD.
| Is This Answer Correct ? | 20 Yes | 2 No |
Post New Answer View All Answers
use of split range ? where it is used ? in which control loop it is used ?
Dear Sir/Madam,im going to attend Hpcl written exams on feb 17th in instrumentation stream..can anyone send me the HPCL model papers and pattern of HPCL ....i ve not yet attended anything in HPCL...so i dont know how it comes...so just i need some model test papers and pattern ..pls help me friends...
our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS
pls give me presant awerness quistion and answer in my emailid.
What is cut off relay? And why use in PLC and DCS?
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
How servomotor controls throttle valve of TURBINE?
how to calculate control valve bonnet size?? or how to select its material?
field bus transmitter calibration procedure tell me
How can test or measure the probe and extension cable to identify if the problem at the probe or cable or at the driver it self? (pleast notify the measuring method)
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
what is stroke check for field instument transmetter's & AOV's
Any one can help me to identified, how can we interchange the device in FF